Common Precautions
Fan Replacement
The service life of the fan is approximately 50,000 hours (at 25°C).
The service life varies, however, depending on the ambient
temperature or other surrounding environmental conditions such as
dust. As a preventive maintenance measure, replace the fan within
approx. two years if it is used at an ambient temperature of 40°C.
Purchase the S82Y-JX FAN Replacement Fan (sold separately) to
replace the fan.
Replace the fan as shown in the following illustration.
Please contact your OMRON sales representative regarding fan
replacement. Fans will be replaced at cost. In addition, a
replacement fan unit (Model S82Y-JXP@@FAN) is available.
Please use the curve below as a guideline for the timing of fan
replacement.
Fan replacements made by the customer fall outside the scope of
safety standards.
Replacement should be implemented as shown below.
S8JX-G Series 300-W 5V, 12V/600-W Model
Fan Set:
Fan (above), instruction sheet
S8JX-P Series 300-/600-W Models