New Product Uninterruptible Power Supply (UPS) S8BA-LF DC-DC type small UPS mounts on a DIN rail to provide an ideal countermeasure for momentary power losses and power failures in industrial computers (IPC) and controllers. • System reliability greatly improved because 24VDC power supply is backed up for a certain period of time in the event of voltage drop or power failure. • Compactness, weight reduction, and long battery life realized thanks to the adoption of a lithium-ion battery.
S8BA-LF Ratings, Characteristics, and Functions Item Capacity Rated input voltage Input voltage range DC input When standard voltage sensitivity is set 24 VDC±10% When low voltage sensitivity is set 24 VDC±12.5% When high voltage sensitivity is set 24 VDC±5% 240 W 360 W Input for rated input voltage for maximum rated loads connected current 5.
S8BA-LF Nomenclature Front view Enlarged view of the operation panel S8BA-24D24D120LF (120 W) 5 1 2 6 3 4 7 8 9 10 S8BA-24D24D240LF (240 W) 5 1 2 6 3 4 7 S8BA-24D24D360LF (360 W) S8BA-24D24D480LF (480 W) 2 5 1 6 3 4 7 No. 1 Name Function Operation panel Describe the name of each part. 2 DC output terminal block Connect to load lines. (+V), (-V) 3 DC input terminal block Connect to input lines.
S8BA-LF Rear view S8BA-24D24D120LF (120 W) 11 12 S8BA-24D24D240LF (240 W) 11 12 S8BA-24D24D360LF (360 W) S8BA-24D24D480LF (480 W) 11 12 No. Name 11 DIN rail mounting hook 12 DIN rail mounting groove 4 Function Hook the UPS on the DIN rail. Groove for positioning the DIN rail and the UPS.
S8BA-LF Connections Block Diagrams S8BA-24D24D@@@LF Diagram of the Input/output circuit block 24 VDC Input 24 VDC Output FET Normal operation: ON Backup operation: OFF DC-DC converter FET Normal operation: OFF Backup operation: ON Normal operation: ON Backup operation: OFF FET Charge/Discharge Normal operation Backup operation Battery * In normal operation, 24 VDC is output as-is for charging the battery and from the input power supply.
S8BA-LF I/O signal functions Type of output signals Signal Description Backup signal output (BU) Stays ON during backup operation at a power failure. Low battery level signal output (BL) Goes ON when the battery becomes weak during backup operation at a power failure. Trouble signal output (TR) Goes ON when an internal failure of the UPS occurs or when the battery life counter expires.
S8BA-LF Contact signal circuit Signal output (BU, TR, BL, WB) Remote ON/OFF UPS Stop Signal input (BS) BL 5V TR 680 Ω BU WB Remote ON/OFF (+) 4.7 Ω BS Remote ON/OFF (–) COM Precautions when selecting switch mode power supplies When selecting switch mode power supplies, install devices with a capacity larger than the total of the UPS internal power consumption and internal power consumption of connected devices to the input side of the UPS.
S8BA-LF Engineering Data Estimated backup time The backup time varies depending on the capacity of connected devices. After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the backup time. (This is also applied to checking the battery.) 1. Convert the total capacity (power consumption) of the connected devices to watts (W). For the indication of connected devices, check your computer and the rear of the display.
S8BA-LF Derating curve 120 A 100 80 480 W 120 A B 100 80 Load rate (%) 360 W Load rate (%) Load rate (%) 120, 240 W 120 60 60 40 40 40 20 20 20 0 0 10 20 30 40 50 60 Ambient temperature (°C) A: For standard mounting, face-up mounting, stationary mounting C 80 60 0 A B 100 0 0 10 20 30 40 50 60 Ambient temperature (°C) A: For standard mounting, B: For face-up mounting, stationary mounting 0
S8BA-LF When the input power supply recovers while the battery level is Low Input power supply During power failure ON OFF ON Power switch OFF High Low Empty Battery level ON OFF UPS output Indication in the "status display" 0.2 s ON Beeper * OFF 4s 1s Normal operation UPS operating mode Backup operation ON BU signal (OUT) OFF ON BL signal (OUT) OFF ON OFF BS signal (IN) * "Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup.
S8BA-LF Overcurrent protection curve Output voltage (%) 120W, 240W, 360W, 480W * In backup operation 100 80 60 40 20 0 0 20 40 60 80 100 120 Output current (%) Note: 1. In backup operation, the output voltage drops at a load rate of 110% or higher. 2. In normal operation, the output stops when the input protection fuse blows out. Dimensions (Unit: mm) Main body S8BA-24D24D120LF (120 W) 2 100 94 100 2.5 S8BA-24D24D240LF (240 W) 2 148 100 100 2.
S8BA-LF DIN Rail (Order Separately) Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.30.15 4.5 350.3 15 25 10 25 25 10 1,000 (500) * 270.15 15(5) * 25 1 * Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) PFP-100N2 16 4.5 35±0.3 27 15 25 10 25 25 10 1,000 25 15 24 29.2 1 1.5 End Plate PFP-M 10 6.2 M48 panhead screw 1.8 1 50 1.8 35.5 35.3 11.5 10 M4 spring washer 1.3 4.8 Note: 1.
S8BA-LF Safety Precautions Warning Indications Caution Warning Indicates a potentially hazardous situation that, if not avoided, could result in serious injury or death. Additionally there may be significant property damage. Caution Indicates a potentially hazardous situation that, if not avoided, could result in minor or moderate injury or property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing to use the product safely.
S8BA-LF Do not exceed the ranges specified for environmental conditions during use/storage. Do not install or store the unit in the places listed below. • Do not store in places where the humidity is lower than 10% or higher than 90%. • Do not use the unit in places where the ambient temperature is lower than 0°C or higher than 55°C. (With no condensation) • Do not use in places where the humidity is lower than 10% or higher than 90%.
S8BA-LF (for maintenance) When maintaining the connected equipment, turn OFF the unit’s “Power” switch to stop the output, and stop the supply of the “input power supply”. • Even if the input power supply to the UPS is stopped while it is in operation, the power output of his unit does not stop and power is supplied from the battery. Do not disassemble, repair, or modify the unit. • Doing so may cause an electric shock or a fire. If fluid leaks from the interior, do not touch the fluid.
S8BA-LF For Storage Face-up mounting To store the UPS for a long time, store it in an environment where the ambient temperature is 25°C or lower, and charge the battery once every year for 10 to 15 minutes. • The battery discharges itself even if it is not used. If the battery is left unused for a long time, it goes into a state of over-discharge. In such a case, the backup time may become shorter, or the battery cannot be used anymore.
S8BA-LF Stationary installation Battery check schedule and frequency Do not mount on floor with front side down Do not stack Ambient temperature 6-Month Inspection 3-Month Inspection 55°C 1 year from the date Up to 1 year from the of purchase and date of purchase afterward 50°C 1.5 years from the Up to 1.
S8BA-LF Conformance to UL Conformance to UL • This product must be installed within a control panel with an internal heater or other unit to protect against the formation of condensation. • Gaps in the door to the control panel must be completely filled or covered with gaskets or other material. • For use as a UL compliant device, the specifications for S8BA24D24D480LF become as follows: • Maximum input current: 20 A • Rated output current/capacity: 16.7 A/400 W • For use in Pollution Degree 2 Environment.
Uninterruptible Power Supply (UPS) S8BA-SBF DC-DC type small UPS mounts on a DIN rail to provide an ideal countermeasure for momentary power losses and power failures in industrial computers (IPC) and controllers. • System reliability greatly improved because 24VDC power supply is backed up for a certain period of time in the event of voltage drop or power failure. • Compactness, weight reduction, and long battery life realized thanks to the adoption of a lithium-ion battery.
S8BA-SBF Ordering Information Main body Uninterruptible Power Supply (UPS) / Control Unit Part Input voltage 24 VDC Output voltage 24 VDC Output current/capacity Model number 20 A/480 W S8BA-24D24D480SBF 40 A/960 W S8BA-24D24D960SBF Battery unit part Rated voltage Rated capacity Weight Model UPS Model : Required units 25.2 VDC 3900 mAh 1.5 kg S8BA-S480L S8BA-24D24D480SBF 25.2 VDC 7800 mAh 2.
S8BA-SBF Ratings, Characteristics, and Functions Description DC input Capacity 24 VDC Input voltage range 23 to 28 VDC Input maximum current for rated input voltage 21.
S8BA-SBF Description Accessory functions Capacity 480 W 960 W Remote ON/OFF signal logic setting; Battery life counter setting; Maximum backup time setting; Startup battery level setting; Backup stop (BS) signal delay time setting; and Backup (BU) signal delay time setting *1. Guideline for a standard installation. Not a guaranteed value. *2. Unit dimensions excluding the DIN rail stopper. *3.
S8BA-SBF Nomenclature Front view S8BA-24D24D480SBF (1) S8BA-S480L (6) Positive terminal Negative terminal (3) (2) (3) [DC ON] LED (4) [BATT] LED [ALERT] LED (5) No. (1) (2) (3) (4) (6) (7) (8) Name DC input terminal block DC output terminal block Battery connection terminal block LED indicators No.
S8BA-SBF Rear view S8BA-24D24D480SBF S8BA-S480L (9) (9) No. (9) Name DIN rail hook S8BA-24D24D960SBF S8BA-S960L (9) No.
S8BA-SBF Connections Block Diagrams S8BA-24D24D@@@SBF Control unit FET 24 VDC Input 24 VDC Normal operation: ON Output Backup operation: OFF Charge FET Normal operation: ON Backup operation: OFF Battery unit Normal operation: OFF Backup operation: ON FET Battery Normal operation Backup operation Note: 1. In normal operation, 24 VDC is output as-is for charging the battery and from the input power supply.
S8BA-SBF I/O signal functions Type of output signals Signal Description Backup signal output (BU) Stays ON during backup operation at a power failure. Low battery level signal output (BL) Goes ON when the battery becomes weak during backup operation at a power failure. Trouble signal output (TR) Goes ON when an internal failure of the UPS occurs or when the battery life counter expires.
S8BA-SBF Contact signal circuit Signal output (BU, TR, BL, WB) Remote ON/OFF UPS Stop Signal input (BS) BL 3.3 V TR 220 Ω BU WB Remote ON/OFF (+) 100 Ω BS Remote ON/OFF (–) COM Precautions when selecting switch mode power supplies When selecting switch mode power supplies, install devices with a capacity larger than the total of the UPS internal power consumption and internal power consumption of connected devices to the input side of the UPS.
S8BA-SBF Engineering Data Estimated backup time The backup time varies depending on the capacity of connected devices. After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the backup time. (This is also applied to checking the battery.) 1. Convert the total capacity (power consumption) of the connected devices to watts (W). For the indication of connected devices, check your computer and the rear of the display.
S8BA-SBF Derating curve Load rate (%) Load rate (%) Standard mounting (15 mm or more space Contact mounting (Less than 15 mm between the left and right) space between the left and right) 100 80 100 80 60 60 40 40 20 20 0 0 0 10 20 30 40 50 60 0 Ambient temperature (°C) 10 20 30 40 50 60 Ambient temperature (°C) Backup operation sequence in the event of power failure/voltage drop (instantaneous voltage drop) When the input power supply recovers while the battery level is suffici
S8BA-SBF When the input power supply does not recover until the battery becomes empty Input power supply ON OFF Battery restorage High Durling power failure Low Empty ON OFF Output from UPS UPS operating mode Normal operation Backup operation BU signal (OUT)* ON OFF BL signal (OUT)* ON OFF BS signal (IN)* ON OFF * For details, refer to I/O signal functions on page 26.
S8BA-SBF Dimensions (Unit: mm) Control unit S8BA-24D24D480SBF 44 9.5 111.4 31 124 99.4 S8BA-24D24D960SBF 52 9.5 111.4 31 124 99.4 Battery unit S8BA-S480L 111.4 84 9.5 30.7 124 99.4 S8BA-S960L 111.4 9.5 150 30.7 124 99.
S8BA-SBF DIN Rail (Order Separately) Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.30.15 4.5 350.3 15 25 10 25 25 10 1,000 (500) * 270.15 15(5) * 25 1 * Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) PFP-100N2 16 4.5 35±0.3 27 15 25 10 25 25 10 1,000 25 15 24 29.2 1 1.5 End Plate PFP-M 10 6.2 M48 panhead screw 1.8 1 50 1.8 35.5 35.3 11.5 10 M4 spring washer 1.3 4.8 Note: 1.
S8BA-SBF Safety Precautions Warning Indications (When replacing the battery unit) Warning Indicates a potentially hazardous situation that, if not avoided, could result in serious injury or death. Additionally there may be significant property damage. Caution Indicates a potentially hazardous situation that, if not avoided, could result in minor or moderate injury or property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely.
S8BA-SBF Do not use the unit at a location where the operating environment temperature is more than 55°C • The battery deteriorates rapidly. It may result in fire. • If the battery's resin separator is damaged, the battery may be short-circuited inside, and may cause an abnormal heating, smoke, rupture or fire. • Doing so may cause a failure or malfunction of the unit. Do not run this unit in parallel. • Operating this unit in parallel may cause a failure or malfunction.
S8BA-SBF The unit is equipped with an output circuit that can supply power to the connected devices even if the unit stops due to a failure or mis-operation of the internal circuit function. If you want to stop the output, stop the source of the “input power supply”. • Output is continuing even when all indicators of the front panel are off.
S8BA-SBF Precautions for Safe Use Before using • The battery has not been charged at the time of purchase. Be sure to charge it before use. • Connect this unit to the input power supply to charge the battery unit. When moving the unit from a cold place to a warm place, leave it for several hours before using it. • If the unit is promptly turned ON after being moved to a warmer place, condensation may form inside the unit and cause it to fail.
S8BA-SBF Incorrect Installation Method Mounting to the DIN Track • Do not short between the terminals. Doing so may result in electric shock. The protection board inside the battery unit may be damaged due to a short-circuit. Connect each connection cable to the correct connected device. Connect the terminal of each connection cable to the connector port with correct polarity. Be sure to follow the above connection procedure.
S8BA-SBF Conformance to EC Directives This product complies with EC Directives. To ensure that the machine or device in which the this product is used complies with EC Directives, the product must be installed as follows: • This product must be installed within a control panel. • You must use reinforced insulation or double insulation for the direct power supply equipment connected to this product. • Models of this product that comply with EC Directives also conform to the Common Emission Standard.
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron).
· Windows is a registered trademark of Microsoft Corporation in the USA and other countries. · Linux is a trademark or registered trademark of Linus Torvalds in the USA and other countries. · Other company names and product names mentioned in this document are the trademarks or registered trademarks of their respective companies. OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V.