Datasheet

S82S
S82S
3
Engineering Data
Derating Curve
Note: The
derating curve depends on the mounting direction
of
the Power Supply
Load (%)
(B)
(A)
Ambient temperature (
°C)
Standard (vertical)
Mounting Position
Horizontal Mounting
Position
(A) (B)
Overload Protection
The
power supply is provided with an
overload protection function
that
protects the load and the power supply
from possible damage
by overcurrent. When the output current rises above a set value
(105% of the rated output current), the protection function is trig-
gered,
decreasing the output voltage. When the output current falls
within the rated range, the overload protection function is automati
-
cally
cleared.
Output voltage (V)
0 50 100
Rated voltage
Output
current (%)
Dual Output Models
+V
output is provided with an overload protection that protects the
load
and the power supply by detecting
total load value of +V and –V
output. It operates at 105% min. of the rated current of +V output
when
–V output is producing the rated output, but this condition va
-
ries
depending on –V output status. –V output has an independent
short-circuit
protection feature.
Inrush Current, Startup Time, Hold
Time
Input ON
AC
input
voltage
Inrush current on input application
AC
input
current
Output
voltage
100 ms (max.) startup time
Input OFF
20 ms (min.)
hold time
90%
96.5%