G2RV-SR G3RV-SR
Common AccessoriesCommon Precautions
Characteristics
Approved standards
UL 508 (file No.E64562)
TÜV(EN 62314)
Item G3RV-SR700/500-A G3RV-SR700/500-AL G3RV-SR700/500-D
Operate time
1/2 cycle of load power supply
+1 ms max.
3 ms max. 6 ms max.
Release time 60 ms max. 60 ms max. 60 ms max.
Output ON voltage drop 1.6 V (RMS) max.
Output ON resistance 0.3 max. (at 24 VDC)
Leaked current 5 mA max. (at 200 VAC, 50/60 Hz) 10 µA max. (at 24 VDC)
Insulation resistance 100 M min. (at 500 VDC)
Dielectric strength Between input and output 2,500 VAC 50/60 Hz 1 min
Vibration resistance Malfunction: 10 to 55 to 10 Hz double amplitude 0.70 mm
Shock resistance 300m/s
2
Ambient operating temperature
Storage: –30 to +100°C (with no icing or no condensation)
Operating: –30 to +55°C (with no icing or no condensation)
Ambient operating humidity 45 to 85% RH
Weight Approx. 38 g
Pollution degree 2
The degree of protection by
IEC60529
IP20
Rated impulse dielectric
strength
4.0 kV/III
Load category LC-A DC-12
Overload current profile
1.5Ie 1.1Ue
5s ON, 10s OFF, 10 cycles
Rated insulation voltage 240 V
Model Input ratings Contact ratings
G3RV-SR700/500-D series
12, 24 VDC
24, 48 VAC/VDC
100, 110, 200, 230 VAC
24 VDC 3 A (resistive load) at 25°C
G3RV-SR700/500-A(L) series
12, 24 VDC
24, 48 VAC/DC
100, 110, 200, 230 VAC
240 VAC 2 A (resistive load) at 25°C
Model Input ratings Contact ratings
G3RV-SR700/500-D series
12, 24 VDC
24, 48 VAC/VDC
100, 110, 200, 230 VAC
24 VDC 3 A (resistive load)
G3RV-SR700/500-A(L) series
12, 24 VDC
24, 48 VAC/VDC
100, 110, 200, 230 VAC
240 VAC 2 A (resistive load)