Datasheet

MYK
26
MY
MYQ
·
MYH
MYK
Common Options (Order Separately)
Common Precautions
Ratings and Specifications
Ratings
Operating coil (AC)
Note: 1. The rated current for AC is the value measured with a DC ammeter in half-wave rectification.
2. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20% for AC rated current and ±15% for DC coil
resistance.
3. The AC coil resistance is a reference value only.
4. Operating characteristics were measured at a coil temperature of 23°C.
5. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*There is variation between products, but actual values are 80% maximum.
Contact Ratings
Characteristics
Note: The data shown above are initial values.
*1. Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*2. Measurement conditions: With rated operating power applied, not including contact bounce.
*3. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4. Ambient temperature condition: 23°C
*5. This value was measured at a switching frequency of 120 operations per minute.
*6. With no icing or condensation.
Rated voltage (V)
Set coil Reset coil
Must
operate
voltage (V)
Must
release
voltage (V)
Maximum
voltage (V)
Power consumption (VA, W)
Rated current
(mA)
Coil resistance
(Ω)
Rated current
(mA)
Coil resistance
(Ω)
Set coil Reset coil
50 Hz 60 Hz 50 Hz 60 Hz
AC
12 57 56 72 39 38.2 130
80% max.* 80% max.
110% max.
of rated
voltage
Approx. 0.6
to 0.9
(at 60 Hz)
Approx. 0.2
to 0.5
(at 60 Hz)
24 27.4 26.4 320 18.6 18.1 550
100 7.1 6.9 5,400 3.5 3.4 3,000
DC
12 110 110 50 235
Approx. 1.3 Approx. 0.6
24 52 470 25 940
48 27 1,800 16 3,000
Number of poles (contact configuration) 2-pole (DPDT)
Contact structure Single
Load Resistive load Inductive load (
cos
ϕ
= 0.4, L/R = 7 ms)
Rated load
3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current 3 A
Maximum switching voltage 250 VAC, 125 VDC
Maximum switching current 3 A
Maximum switching power
660 VA
72 W
176 VA
36 W
Contact material Au plating + Ag
Contact resistance*1 50 mΩ max.
Set
Operate time*2 AC: 30 ms max., DC: 15 ms max.
Minimum pulse width AC: 60 ms, DC: 30 ms
Reset
Release time*2 AC: 30 ms max., DC: 15 ms max.
Minimum pulse width AC: 60 ms, DC: 30 ms
Maximum
switching
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3 100 MΩ min.
Dielectric
strength
Between coil and contacts
Between contacts of
different polarity
1,500 VAC at 50/60 Hz for 1 min
Between contacts of the
same polarity
1,000 VAC at 50/60 Hz for 1 min
Between set/reset coils
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s
2
Malfunction 200 m/s
2
Endurance
Mechanical 100,000,000 operations min. (switching frequency: 18,000 operations/h)
Electrical*4 200,000 operations min. (at rated load, switching frequency: 1,800 operations/h)
Failure rate P value (reference value)*5 1 mA at 1 VDC
Ambient operating temperature*6 55 to 60°C
Ambient operating humidity 5% to 85%
Weight Approx. 30 g