Datasheet

27
MY
Plastic Sealed Relays: MYQ
Characteristics
Contact resistance
*
1
50 m
Ω
max.
Note: The values at the left are initial
values.
*1. Measurement conditions: 1 A at 5
VDC using the voltage drop
method
*2. Measurement conditions: With
rated operating power applied, not
including contact bounce.
Ambient temperature condition:
23° C
*3. Measurement conditions: For 500
VDC applied to the same location
as for dielectric strength
measurement.
*4. This value is for bifurcated
contacts.
*5. Ambient temperature condition:
23° C
Operation time
*
2
20 ms max.
Release time
*
2
20 ms max.
Maximum
operating
frequency
Mechanical
18,000 operations/h
Rated load
1,800 operations/h
Dielectric
strength
Between coil and contacts
1,500 VAC at 50/60 Hz for 1 min.
Between contacts of different polarity
1,500 VAC at 50/60 Hz for 1 min.
Between contacts of the same polarity
1,000 VAC at 50/60 Hz for 1 min.
Insulation resistance
*
3
100 M
Ω
min.
Vibration
resistance
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction
1,000 m/s
2
Malfunction
200 m/s
2
Endurance
Mechanical
AC: 50,000,000 operations (5,000,000
*
4
) min., DC: 100,000,000 operations
(5,000,000
*4
) min. (switching frequency: 18,000 operations/h)
Electrical
*
5
200,000 operations min. (100,000 operations
*4
) (rated load, switching
frequency: 1,800 operations/h)
Weight
Approx. 35 g
Ratings and Specifications
Ratings
Operating Coil
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of
+15%/
20% for AC rated current and ±15% for DC coil resistance.
2.
The AC coil resistance and coil inductance values are reference values only.
3.
Operating characteristics were measured at a coil temperature of 23°C.
4.
The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.
There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2.
There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC.
To ensure release, use a value that is lower than the specified value.
Contact Ratings
* This value was measured at a switching frequency of 120 operations per minute.
* With no icing or condensation.
Item
Rated current (mA)
Coil resis-
tance (
Ω
)
Coil inductance (H)
Must-
operate
voltage (V)
Must-
release
voltage (V)
Maximum
voltage (V)
Power
consumpti
on (VA, W)
Rated voltage (V)
50 Hz 60 Hz
Armature OFF
Armature ON
AC
24
53.8 46 180 0.69 1.3
80%
max.
*
1
30%
min.
*
2
110% of
rated
voltage
Approx.
0.9 to 1.3
(at 60 Hz)
100/110
11.7/12.9
10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 91.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12
75 160 0.734 1.37
10%
min.
*
2
Approx.
0.9
24
36.9 650 3.2 5.72
48
18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.0
Type
Item
Resistive load
Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 1 A at 220 VAC, 1 A at 24 VDC 0.5 A at 220 VAC, 0.5 A at 24 VDC
Rated carry current 1 A
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 1 A
Maximum switching capacity
(reference value)
220 VAC, 24 W 110 VAC, 12 W
Failure rate P value
(reference value)
Single contacts: 1 mA at 1 VDC, Bifurcated contacts: 100 µA at 1 VDC
Contact structure Single/bifurcated
Contact materials Au plating + Ag
Ambient operating temperature 55 to 60° C
*
Ambient operating humidity 5% to 85%
Ordering Information
Relays with Plug-in or Soldered
Terminals
Relays with PCB Terminals
Type 4 poles
Classification Model
Rated voltage (V)
Models
with single
contacts
Standard
models
MYQ4
100/110, 110/
120, 200/220, or
220/240 VAC
24 VDC
Models
with built-
in
operation
indicators
MYQ4N
24, 100/110,
110/120,
200/220, or
220/240 VAC
12, 24, 48, or
100/110 VDC
Bifurcated
contacts
Standard
models
MYQ4Z
100/110,
110/120, or
200/220 VAC
12 or 24 VDC
Type 4 poles
Classification Model
Rated voltage
(V)
Models with
single contacts
MYQ4-02
50, 200/220, or
220/240 VAC
24 VDC
Bifurcated
contacts
MYQ4Z-02
100/110 VAC
24 or 48 VDC
Whenyourorder,specifytheratedvoltage.