Datasheet
MY
18
Case-surface-mounting Relays: MY@F
Ordering Information
Note: 1. Ask your OMRON representative for details on the time required to deliver made-to-order products.
2. Ask your OMRON representative for details on product specifications and the ability to manufacture products with voltages other than the above coil
specifications.
Ratings and Specifications
Ratings
Operating Coil (Standard Models)
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/
−
20% for the AC rated current and ±15% for the DC coil resistance.
2.
The AC coil resistance and inductance values are reference values only (at 60 Hz).
3.
Operating characteristics were measured at a coil temperature of 23°C.
4.
The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.
There is variation between products, but actual values are 80% max.
To ensure operation, apply at least 80% of the rated value
*2.
There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure release, use a value that is lower than the specified value.
Contact Ratings
* With no icing or condensation.
Number of poles Classification Model
Rated voltage (V)
Standard products Made-to-order items
2 poles
Models with single
contacts
MY2F
24, 110/110, 100/120 or 200/220 VAC 220/240 VAC
12 or 24 VDC 48 or 100/110 VDC
3 poles
Models with single
contacts
MY3F
100/110 VAC 24 or 200/220 VAC
--- 24 or 100/110 VDC
4 poles
Models with single
contacts
MY4F
100/110 or 200/220 VAC 24 or 110/120 VAC
12 or 24 VDC 48 or 100/110 VDC
Bifurcated contacts MY4ZF
200/220 VAC ---
--- 12 or 24 VDC
Item Rated current (mA)
Coil
resistance (Ω)
Coil inductance (H)
Must-operate
voltage (V)
Release
voltage (V)
Maximum
voltage (V)
Power consumption
(VA, W)
Rated voltage (V) 50 Hz 60 Hz Armature OFF Armature ON
AC
24 53.8 46 180 0.69 1.3
80% max.
*1
30% min.
*2
110% of
rated voltage
Approx. 0.9 to 1.3
(at 60 Hz)
100/110
11.7/12.9 10/11 3,750 14.54 24.6
110/120
9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220
6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240
4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC
12 75 160 0.73 1.37
10% min.
*2
Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110
9.1/10 11,000 45.6 86.2
Refer to the standards certifications and compliance
section of your OMRON website for the latest
information on certified models.
Whenyourorder,specifytheratedvoltage.
Number of poles 2 or 3 poles 4 poles
Load
Item
Resistive load
Inductive load
(cos φ = 0.4, L/R = 7 ms)
Resistive load
Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load
5 A at 220 VAC
5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current
5 A 3 A
Maximum contact voltage
250 VAC, 125 VDC 250 VAC, 125 VDC
Maximum contact current
5 A 3 A
Contact configuration
DPDT, 3PDT 4PDT
Contact structure
Single Single
Contact materials
Ag Au plating + Ag
Type
Item
Standard models
Ambient operating temperature
*
−55 to 70° C
Ambient operating humidity 5% to 85%