Datasheet
CSM_G7S-_-E_DS_E_6_2
1
Relays with Forcibly Guided Contacts
G7S-@-E
Relays with Forcibly Guided
Contacts and High Switching
Capacity of 10A
• Relays with forcibly guided contacts
(EN50205 Class A, certified by VDE).
• Supports the CE marking of machinery (Machinery
Directive).
• Helps avoid hazardous machine status when used as part
of an interlocking circuit.
• Track-mounting and Back-mounting Sockets are
available.
Model Number Structure
Model Number Legend
1. NO Contact Poles
4: 4PST-NO
3: 3PST-NO
2. NC Contact Poles
2: DPST-NC
3: 3PST-NC
Ordering Information
Relays with Forcibly Guided Contacts
Sockets
Specifications
Ratings
Coil
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±15%.
2. The maximum voltage is based on an ambient operating temperature of 23°C maximum.
Be sure to read the “Safety Precautions” on page 4 and the
“Precautions for All Relays with Forcibly Guided Contacts”.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
G7S-@A@B-E
1 2
Type Poles Contact configuration Rated voltage Model
Standard 6 poles
4PST-NO, DPST-NC
24 VDC
G7S-4A2B-E
3PST-NO, 3PST-NC G7S-3A3B-E
Type4 Rated voltage Model
Track-mounting Common for track mounting and screw mounting 24 VDC P7S-14F-END
Back-mounting PCB terminals --- P7S-14P-E
Item
Rated voltage
Rated current
(mA)
Coil resistance
(Ω)
Max. voltage
(V)
Power consumption
(W)
24 VDC 30 800 110% Approx. 0.8