Datasheet
Machine Automation Controller NX1P
17
*1. Execution objects and variable tables (including variable names)
*2. Memory used for CJ-series Units is included.
*3. The value can be set in 1 ch increments. The value is included in the total size of variables without a Retain attribute.
*4. The value can be set in 1 ch increments. The value is included in the total size of variables with a Retain attribute.
*5. Refer to the NJ/NX-series CPU Unit Motion Control User’s Manual (Cat. No. W507) for the description of this term.
*6. Data will be refreshed at the set interval, regardless of the number of nodes.
*7. “pps“ means packets per second, i.e., the number of communications packets that can be sent or received in one second.
*8. As the EtherNet/IP port implements the IGMP client, unnecessary multi-cast packets can be filtered by using an Ethernet switch that supports
IGMP Snooping.
Built-in
EtherNet/IP
port
CIP message
service:
Explicit messages
Class 3 (number of connections)
32
(clients plus server)
UCMM
(non-connection
type)
Maximum number of clients that
can communicate at one time
32
Maximum number of servers that
can communicate at one time
32
Number of TCP sockets 30
Built-in
EtherCAT port
Communications standard IEC 61158 Type12
EtherCAT master specifications Class B (Feature Pack Motion Control compliant)
Physical layer 100BASE-TX
Modulation Baseband
Baud rate 100 Mbps (100BASE-TX)
Duplex mode Auto
Topology Line, daisy chain, and branching
Transmission media
Twisted-pair cable of category 5 or higher
(double-shielded straight cable with aluminum tape and braiding)
Maximum transmission distance between nodes 100 m
Maximum number of slaves 16
Range of node addresses that can be set 1 to 192
Maximum process data size
Input: 1,434 bytes
Output: 1,434 bytes
However, the maximum number of process data frames is 1.
Maximum process data size per slave
Input: 1,434 bytes
Output: 1,434 bytes
Communications cycle 2,000 μs to 8,000 μs in 250-μs increments
Sync jitter 1 μs max.
Serial
Communications
(Serial
Communications
Option Board)
Communications method half duplex
Synchronization Start-stop
Baud rate 1.2/2.4/4.8/9.6/19.2/38.4/57.6/115.2 kbps
Transmission distance Depends on Option Board.
Supported protocol Host link, Modbus-RTU master, and no-protocol
Unit
configuration
Maximum number
of connectable
Units
Maximum number of NX Units that can be
mounted to the CPU Unit
8
Maximum number of NX Units for entire controller
24
On CPU Rack: 8
On EtherCAT Slave Terminals: 16
Power supply
Model A non-isolated power supply for DC input is built into the CPU Unit.
Power OFF detection time 2 to 8 ms
Option Board Number of slots 221
Built-in I/O
Input Number of points 24 24 14
Output
Number of points 16 16 10
Load short-circuit protection
11DT/10DT/9024DT: Not provided (NPN)
11DT1/10DT1/9024DT1: Provided (PNP)
Internal clock
Accuracy
At ambient temperature of 55°C: -3.5 to 0.5 min error per month
At ambient temperature of 25°C: -1.5 to 1.5 min error per month
At ambient temperature of 0°C: -3 to 1 min error per month
Retention time of built-in capacitor At ambient temperature of 40°C: 10 days
Item
NX1P2-
11/
111
10/
101
90/