Using Twisted Wires/Solid Wires
If you use the twisted wires or the solid wires, use the following table to determine the correct wire specifications.
*1 Secure wires to the screwless clamping terminal block. Refer to the Securing Wires in the USER'S MANUAL for how to secure wires.
*2 With the NX-TB@@@1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid wire.
<Additional Information> If more than 2 A will flow on the wires, use plated wires or use ferrules.
Terminals
Wire type
Wire size
Conductor length
(stripping length)
Twisted wires Solid wire
Classification Current capacity Plated Unplated Plated Unplated
All terminals except
ground terminals
2 A max.
Possible
Possible Possible Possible
0.08 to 1.5 mm
2
AWG28 to 16
8 to 10 mm
Greater than
2 A and 4 A or less
Not
Possible
Possible
*1
Not
Possible
Greater than
4 A
Possible
*1
Not
Possible
Ground terminals --- Possible Possible
Possible
*2
Possible
*2
2.0 mm
2
9 to 10 mm
Conductor length (stripping length)