Accessories
End Cover (NX-END01)
One End Cover is provided together with the EtherNet/IP Coupler Unit.
General Specification
Item Specification
Enclosure Mounted in a panel
Grounding method Ground to 100 Ω or less
Operating
environment
Ambient operating temperature 0 to 55°C
Ambient operating humidity 10% to 95% (with no condensation or icing)
Atmosphere Must be free from corrosive gases.
Ambient storage temperature 25 to 70°C (with no condensation or icing)
Altitude 2,000 m max.
Pollution degree Pollution degree 2 or less: Conforms to JIS B 3502 and IEC 61131-2.
Noise immunity Conforms to IEC 61000-4-4. 2 kV (power supply line)
Overvoltage category Category II: Conforms to JIS B 3502 and IEC 61131-2.
EMC immunity level Zone B
Vibration resistance
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s
2
, 100 min each in
X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistance Conforms to IEC 60068-2-27. 147 m/s
2
, 3 times each in X, Y, and Z directions
Applicable standards
cULus: Listed UL508 and ANSI/ISA 12.12.01
EC: EN 61131-2 and C-Tick
Protrusions for removing the Unit
Unit hookup guide
Unit hookup guide
Protrusions for removing the Unit