Datasheet
44 Remote I/O
System unit
Shield connection unit (grounding terminal)
Item Specifications
Model NX-TBX01
Name Shield connection unit
Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max.
Insulation resistance 20 M min. between isolated circuits (at 100 VDC)
Isolation method Isolation between the SHLD functional ground terminal and internal circuit: no-isolation
Unit power consumption 0.45 W max.
I/O current consumption No consumption
Terminal block type Screwless push-in terminal
16 terminals (A + B with FG)
Number of
shield terminals
14 terminals (the following two terminals are Functional Ground terminals)
Dimensions (W x H x D) 12 × 100 × 71 mm
Weight 65 g max.
Terminal wiring
NX-TBX01
A1 B1
A8 B8
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
A
Z
B
NC
IOV
IOG
IOV
IOG
I0
I2
I1
NC
IOV
IOG
IOV
IOG
A1
A8
B1
B8
Shield
Rotary encorder
Internal circuits
NX unit power supply
NX unit power supply
I/O power supply
I/O power supply
NX unit power supply
NX unit power supply
I/O power supply
I/O power supply
…
SHLD terminal
SHLD terminal
SHLD terminal
Circuit layout
NX-TBX01
Terminal
block
NX bus
connector
(left)
NX bus
connector
(right)
(Functional ground
terminal)
(Functional ground
terminal)
DIN track contact plate
(unit back surface)
Ground of 100
or less
Shield
connection unit
NX-TBX01
Incremental encorder
input unit
(open collector input)