General Specifications
NS5/NS8/NS10/NS12/NS15
*1. Operate the PT within the temperature and humidity ranges shown in the right diagram.
*2. Support for NS5, NS10, NS12 and NS15.
NSH5 Hand-held PT
Series NS5-V2 NS8-V2 NS10-V2 NS12-V2 NS15-V2
Rated power supply
voltage
24 VDC
Allowable voltage range 20.4 to 27.6 VDC (24 VDC 15%)
Power consumption 15 W max. 25 W max. 45 W max.
Ambient operating
temperature
0 to 50 C (See note on the next page.)
Note: The ambient operating temperature is subject to the following restrictions according to
the mounting angle.
Mounting angle of 0 to 30 to the horizontal:
• When no Expansion Units are mounted, the operating temperature range is 0 to 45C.
• When a Video Input Unit or a Controller Link Interface Unit is mounted, the ambient
operating temperature is 0 to 35C.
Mounting angle of 30 to 90 to the horizontal: Operating temperature range of 0 to 50C
Storage temperature 20 to 60 C *1
Ambient operating
humidity
35 to 85% (0 to 40 C), 35 to 60% (40 to 50 C) (with no condensation)
Operating environment No corrosive gases.
Noise immunity Conforms to IEC61000-4-4, 2 kV (power lines).
Vibration resistance
(during operation)
10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8 m/s
2
30 min each in X, Y, and Z directions
5 to 8.4 Hz, 3.5 mm single
amplitude, 8.4 to 150 Hz,
9.8 m/s
2
10 min times
each in X, Y, and Z
directions
Shock resistance
(during operation)
147 m/s
2
3 times each in direction of X, Y, and Z
Weight 1.0 kg max. 2.0 kg max. 2.3 kg max. 2.5 kg max. 4.2 kg max.
Degree of protection
Front operating panel: Equivalent to IP65 oil-proof type and NEMA4 UL type 4. *2
Note: May not be applicable in locations with long-term exposure to oil.
Ground Ground to 100 or less.
Battery life 5 years (at 25 C): Replace battery within 5 days after the battery runs low (indicator lights orange).
Applicable standards Certified for conformance to UL 508, UL 1604, EMC Directive, NK, and LR Standards.
Series NSH5-V2
Type 5.7-inch Color TFT (Hand-held Version)
Case colour black
Built-in Ethernet port No
Model NSH5-SQR10B-V2 (Emergency stop button: Red) NSH5-SQG10B-V2 (Stop button: Gray)
Rated power supply
voltage
24 VDC
Allowable voltage range 20.4 to 27.6 VDC (24 VDC 15%)
Power consumption 10 W max.
Ambient operating
temperature
0 to 40C
Storage temperature 20 to 60C
Ambient operating
humidity
35% to 85% (0 to 40C) with no condensation
Operating environment No corrosive gases.
Noise immunity
Common mode: 1,000 Vp-p (between power supply terminals and panel)
Normal mode: 300 Vp-p
Pulse width: 100 ns to 1 s, Rise time: 1-ns pulse
Vibration resistance
(during operation)
10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8 m/s
2
30 min each in X, Y, and Z directions
Shock resistance
(during operation)
147 m/s
2
3 times each in direction of X, Y, and Z
Weight 1 kg max.
Degree of protection Equivalent to IP65.
Ground Ground to 100 or less.
Battery life 5 years (at 25C): Replace battery within 5 days after the battery runs low (indicator lights orange).
Applicable standards Certified for conformance to UL 508, EMC Directive, and EN 60204-1.
90°
Display surface
30°
Horizontal 0°
60
50
40
30
20
10
0
Temperature (°C)
Temperature (°C)
Humidity (%RH)
8070605040302010020
10%
20%
35%
40%
60%
80%95%
Storage
Operation
Order/version: 2447841/010 (width: 210mm, height: 297mm)
Print type: NS Brochure - Central Print, Full color, with extra spotcolor(s)
Produced by Adnovate on 03-apr-2012 at 10:46:40 in Adobe InDesign 7.0.4.553
Low resolution proof not suitable for production purposes
Page: 39