Datasheet

K8DT-PZ
2
Ratings and Specifications
Ratings Specifications
Rated input voltage
K8DT-PZ1@N: Three-phase, three-wire Mode:
200, 220, 230, or 240 VAC
K8DT-PZ2@N: Three-phase, three-wire Mode:
380, 400, 415, or 480 VAC
Input load
K8DT-PZ1: Approx. 1.7 VA
K8DT-PZ2: Approx. 2.7 VA
Rated insulation voltage
528 VAC
Operating value setting
range
Overvoltage/Undervoltage
2% to 30% of rated input voltage
Asymmetry
5% to 22% of rated input voltage
Note: The rated input voltage can be switched
by using the DIP switches.
Operating value
Overvoltage/Undervoltage
Operates at 100% of set value.
Asymmetry
Asymmetry operating value = Rated input
voltage Asymmetry set value (%)
The asymmetry operation will function when the
potential difference between the highest and
lowest voltage phases equals or exceeds the
asymmetry operating value.
Reset value 2% of operating value (fixed)
Reset method Automatic reset
Operating
time
setting
range
Overvoltage/
Undervoltage
0.1 to 30 s
Asymmetry 0.1 to 30 s
Phase
sequence
0.1 s0.05 s
Phase loss 0.1 s max.
Power ON lock time
(LOCK)
1 s/5 s (switched by using the DIP switch)
Indicators
Power (PWR): Green, Output (OUT): Yellow,
Alarm outputs (ALM): Red
Output form
Relay Output: SPDT contact
Transistor Output: 1
Output relay ratings
Rated load
5 A at 250 VAC (Resistive load)
5 A at 30 VDC (Resistive load)
1 A at 250 VAC (Inductive load)
0.2 A at 48 VDC (Inductive load)
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC:
50,000 operations
3 A at 250 VAC or 30 VDC:
100,000 operations
Transistor output
ratings
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
Maximum current: 50 mA DC
Ambient operating
temperature
20 to 60°C (with no condensation or icing)
Storage temperature 25 to 65°C (with no condensation or icing)
Ambient operating
humidity
25% to 85% RH (with no condensation)
Storage humidity 25% to 85% RH (with no condensation)
Altitude 2,000 m max.
Applicable wires Stranded wires, solid wires, or ferrules
Applicable wire size 0.25 to 1.5 mm
2
(AWG24 to AWG16)
Wire insertion force 8 N max. for AWG20 wire
Screwdriver insertion
force
15 N max.
Wire stripping length 8 mm
Ferrule length 8 mm
Recommended flat-
blade screwdriver
XW4Z-00B (Omron)
SZF 0.4 2.5 (Phoenix Contact)
210-719 (Wago)
SDI 0.4 2.5 75 (Weidmuller)
Current capacity 10 A (per pole)
Number of insertions 50 times
Case color N1.5
Case material PC, UL 94 V-0
Weight Approx. 100 g
Mounting Mounts to DIN Track, or screw mounting
Dimensions 17.5 90 90 mm (WDH)
Input frequency 50/60 Hz
Overload capacity Continuous 528 V
Repeat
accuracy
Operating
value
0.5% full scale (at 25C and 65% humidity, rated
power supply voltage)
Operating
time
50 ms (at 25C and 65% humidity, rated power
supply voltage)
Applicable
standards
Conforming
standards
EN 60947-5-1
Installation environment (pollution level 2,
Overvoltage category III)
EMC EN 60947-5-1
Safety
standards
UL 60947-5-1 (Listing), Korean Radio Waves Act
(Act 10564), CCC (GB 14048.5), LR (Category
ENV1.2)
Insulation resistance
20 M: min.
Between external terminals and case
Between input terminals and output terminals
Dielectric strength
2,000 VAC for one minute
Between external terminals and case
Between input terminals and output terminals
Impulse withstand
voltage
6 kV (between live terminals and exposed, non-
charged metal parts)
Noise immunity
1,500 V power supply terminal common/normal
mode
Square-wave noise of 1 Ps/100 ns pulse width
with 1-ns rise time
Vibration resistance
Frequency: 10 to 55 Hz, 0.35-mm single
amplitude
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance
100 m/s
2
, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20