Datasheet
K8DT-LS
5
Nomenclature
Front Panel
Note: Use solid wires, stranded wires, or ferrules to connect to the
terminals.
To maintain the withstand voltage after connecting the
terminals, insert 8 mm of exposed conductor into the terminal.
Indicators
Setting Knobs
Operation Method
DIP Switch Settings
The operating mode is set using the DIP switch located on the front of the Unit.
K8DT-LS does not use SW2, SW3 and SW4.
Note: Open the DIP switch cover to set the DIP switch.
Keep the DIP switch cover closed while the power supply to the Relay is ON.
Operating time knob
Operating resistance knob
Power indicator
Output status indicator
Terminal block
(See note.)
Terminal block
(See note.)
8 mm 8 mm
Solid Wire
8 mm
Stranded Wires Ferrules
Item Description
Power indicator (PWR:
Green)
Lit when power is being supplied.
Output status indicator
(Output: Yellow)
Lights for output.
Item Description
Operating resistance knob
Used to set the resistance to 10 k to
100 k.
Operating time knob
Used to set the operating time to 0.1 to
10 s.
O
N
1
2
3
4
SW3
DIP switch pins
SW2
SW1
SW4
DIP Switch Function
Note: All pins are set to OFF by default.
Pin
ON ❍
OFF ●
Operating mode
Automatic liquid
discharge
operation
❍
Not used. Not used. Not used.
Automatic liquid
supply operation
●
1
ON
OFF
2 3
4