Datasheet
K8DT-AS
2
Ratings and Specifications
Input Range
*1. The range is selected using connected terminals.
*2. The K8DT-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.)
Model Range *1 Connection terminal Setting range Input impedance Input type Overload capacity
K8DT-AS1@@
20 mA AC/DC I1-COM 2 to 20 mA AC/DC Approx. 5 Direct input
Continuous input at
120% of maximum input.
1 s at 150%
100 mA AC/DC I2-COM 10 to 100 mA AC/DC Approx. 1 Direct input
500 mA AC/DC I3-COM 50 to 500 mA AC/DC Approx. 0.2 Direct input
K8DT-AS2@@
1 A AC/DC I1-COM 0.1 to 1 A AC/DC
Approx. 0.12
(Load: 0.5 VA)
Direct input or
commercially
available CT
5 A AC/DC I2-COM 0.5 to 5 A AC/DC
Approx. 0.02
(Load: 1.5 VA)
K8DT-AS3@@
100 A AC I2-COM 10 to 100 A AC *2 --- OMRON CT
Continuous input at 120% with an
OMRON CT (K8AC-CT200L).
30 s at 200%
1 s at 600%
* CT capacity on primary side.
200 A AC I3-COM 20 to 200 A AC *2 --- OMRON CT