Datasheet

New Product
1
Single-phase Overvoltage/Undervoltage Relay
K8AK-VW
Ideal for Voltage Monitoring for
Industrial Facilities and Equipment.
Monitor for overvoltages and undervoltages simultaneously.
Separate settings and outputs supported for overvoltages and
undervoltages.
Manual resetting and automatically resetting supported by one
Relay.
Pre-alarm Monitoring Mode.
Two SPDT output relays, 5 A at 250 VAC (resistive load).
Process control signal (0 to 10 V) and current splitter input
supported.
Output status can be monitored using LED indicator.
Input frequency of 40 to 500 Hz supported.
Inputs are isolated from the power supply.
Ordering Information
List of Models
Ratings and Specifications
Input Range
* The range is selected using connected terminals.
Refer to Safety Precautions on page 9.
Refer to page 8 for commonly asked questions.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Setting range Power supply voltage Model
1 to 10 V AC/DC
3 to 30 V AC/DC
15 to 150 V AC/DC
24 VAC/DC K8AK-VW2 24 VAC/DC
100 to 240 VAC K8AK-VW2 100-240 VAC
20 to 200 V AC/DC
30 to 300 V AC/DC
60 to 600 V AC/DC
24 VAC/DC K8AK-VW3 24 VAC/DC
100 to 240 VAC K8AK-VW3 100-240 VAC
Model Range* Connection terminal Setting range Input impedance Overload capacity
K8AK-VW2
0 to 10 V AC/DC V1-COM
1 to 10 V AC/DC
3 to 30 V AC/DC
15 to 150 V AC/DC
Approx. 120 k
Continuous input at 115% of
maximum input.
10 s at 125%
(up to 600 VAC)
0 to 30 V AC/DC V2-COM Approx. 320 k
0 to 150 V AC/DC V3-COM Approx. 1.6 M
K8AK-VW3
0 to 200 V AC/DC V1-COM
20 to 200 V AC/DC
30 to 300 V AC/DC
60 to 600 V AC/DC
Approx. 1.2 M
0 to 300 V AC/DC V2-COM Approx. 1.7 M
0 to 600 V AC/DC V3-COM Approx. 3.1 M

Summary of content (12 pages)