Operation Methods
Connections
Input
Connect to L1, L2, and L3 (for three-phase three-wire mode) or L1, L2, L3, and N (for three-phase four-wire
mode), depending on the mode selected using pin 2 on the DIP switch.
The Unit will not operate correctly if the DIP switch setting and the wiring do not agree.
Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase sequence
is incorrect.
Outputs
Terminals 11, 12, and 14 are the output terminals for overvoltage (SPDT).
Terminals 21, 22, and 24 are the output terminals for undervoltage (SPDT).
* Use the recommended ferrules if you use twisted wires.
DIP Switch Settings
The Startup lock time, number of wires, and rated voltage are set using the DIP switch located on the bottom of the Unit.
Load
Voltage input
Signal output
14
12
L1
L2
L3
11
L1NL2L3
Signal output
24
22
21
Undervoltage
alarm
Overvoltage
alarm
N
SW3
DIP switch pins
ON
OFF
SW2
SW1
SW4
DIP Switch Functions
K8AK-PW1
Note: All pins are set to OFF at the factory.
K8AK-PW2
Note: All pins are set to OFF at the factory.
Pin
OFF
ON
Power ON lock time 1 s --- --- ---
5 s --- --- ---
Number of wires 3-wire 3-phase --- --- ---
4-wire 3-phase --- --- ---
Rated voltage 3-wire 3-
phase
4-wire 3-
phase
200 V 115 V --- --- ●●
220 V 127 V --- --- ❍●
230 V 133 V --- --- ●❍
240 V 138 V --- --- ❍❍
Pin
OFF
ON
Power ON lock time 1 s --- --- ---
5 s --- --- ---
Number of wires 3-wire 3-phase --- --- ---
4-wire 3-phase --- --- ---
Rated voltage 3-wire 3-
phase
4-wire 3-
phase
380 V 220 V --- --- ●●
400 V 230 V --- --- ❍●
415 V 240 V --- --- ●❍
480 V 277 V --- --- ❍❍
1
OFF
ON
2 3 4
1
OFF
ON
2 3 4