Datasheet

K8AK-PW
3
Specifications
Input frequency range 50/60 Hz
Overload capacity Continuous input at 115% of maximum input. 10 s at 125%. (up to 600 VAC)
Repeat accuracy Operating value ±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, DC and 50/60
Hz sine wave input)
Operating time ±50 ms (at 25°C and 65% humidity, rated power supply voltage)
Applicable
standards
Conforming standards EN 60947-5-1
Installation environment (pollution level 2, installation category III)
EMC EN 60947-5-1
Safety standards UL 508 (Recognition), Korean Radio Waves Act (Act 10564),
CSA: C22.2 No.14, CCC: GB14048.5
Insulation resistance 20 M
Between all external terminals and the case
Between all input terminals and all output terminals
Dielectric strength 2,000 VAC for 1 min
Between all external terminals and the case
Between all input terminals and all output terminals
Noise immunity 1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Vibration resistance
Frequency: 10 to 55 Hz, acceleration 50 m/s
2
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance 100 m/s
2
, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20
0
10
20
30
40
50
60
51015
Distance between products d [mm]
Ambient temperature [°C]
K8AK
No.3
K8AK
No.2
K8AK
No.1
K8AK
No.4
K8AK
No.5
DIN Track Distance between products: d
Sample: K8AK-PW
Mounting distances: 0, 5, and 10 mm min.
Test method
Relationship of Mounting Distance between K8AK-PW Relays
and Ambient Temperature (Reference Values)
The following diagram shows the relationship between the mounting distances and the
ambient temperature.
If the relay is used with an ambient temperature that exceeds these values, the temperature
of the K8AK may rise and shorten the life of the internal components.