Datasheet

New Product
1
Three-phase Voltage and Phase-sequence Phase-loss Relay
K8AK-PM
Ideal for Monitoring 3-phase Power
Supplies for Industrial Facilities and
Equipment.
Greater resistance to inverter noise.
Monitor overvoltages, undervoltages, phase sequence,
and phase loss for three-phase 3-wire or 4-wire power
supplies with just one Unit.
Switch setting for 3-phase 3-wire or 3-phase 4-wire power
supply.
Two SPDT output relays, 5 A at 250 VAC (resistive load).
Output overvoltages and undervoltages using separate
relays.
World-wide power specifications supported by one Unit
(switchable).
Output status can be monitored using LED indicator.
Ordering Information
List of Models
Note: Three-phase 3-wire or 4-wire and the input range are switched using a DIP switch.
* The power supply voltage is the same as the rated input voltage.
Single K8AK Monitors 3-phase Power Supply with 3 or 4 Wires
Monitoring Relays can be used to monitor 3-phase power supplies with 3 or 4 wires simply by changing DIP switch settings.
A Single K8AK Can Monitor a 3-phase Power Supply Anywhere in the World
Reduces Maintenance Parts Inventory
Refer to Safety Precautions on page 10.
Refer to page 8 to 9 for commonly asked questions.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Rated input* Model
3-phase 3-wire mode 200, 220, 230, 240 VAC K8AK-PM1
3-phase 4-wire mode 115, 127, 133, 138 VAC
3-phase 3-wire mode 380, 400, 415, 480 VAC K8AK-PM2
3-phase 4-wire mode 220, 230, 240, 277 VAC
SW3 ON OFF ON OFF
SW4 ON ON OFF OFF
K8AK-PM1
SW2
ON P-N 138 V 133 V 127 V 115 V
OFF P-P 240V 230 V 220 V 200 V
K8AK-PM2
SW2
ON P-N 277 V 240 V 230 V 220 V
OFF P-P 480 V 415 V 400 V 380 V
Phase to phase voltage (3 wires)
Phase to neutral voltage (4 wires)
L1 L2 L3 L1 L2 L3 N
400VAC
400VAC
400VAC
230VAC
230VAC
230VAC

Summary of content (16 pages)