Datasheet

K8AK-PA
3
Specifications
Input frequency 50/60 Hz
Overload capacity
Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC).
Repeat accuracy
Operating value ±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, 50/60 Hz sine wave input)
Operating time
±50 ms (at 25°C and 65% humidity, rated power supply voltage)
Applicable stan-
dards
Conforming standards
EN 60947-5-1
Installation environment (pollution level 2, installation category III)
EMC
EN 60947-5-1
Safety standards
UL 508 (Recognition), Korean Radio Waves Act (Act 10564),
CSA: C22.2 No.14, CCC: GB/T 14048.5
Insulation resistance
20 MΩ min.
Between external terminals and case
Between input terminals and output terminals
Dielectric strength
2,000 VAC for one minute
Between external terminals and case
Between input terminals and output terminals
Noise immunity
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 μs/100 ns pulse width with 1-ns rise time
Vibration resistance
Frequency: 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance
100 m/s
2
, 3 times each in 6 directions along 3 axes
Degree of protection
Terminals: IP20
0
10
20
30
40
50
60
51015
Distance between products d [mm]
Ambient temperature [°C]
K8AK
No.3
K8AK
No.2
K8AK
No.1
K8AK
No.4
K8AK
No.5
DIN Track Distance between products: d
Sample: K8AK-PA
Mounting distances: 0, 5, and 10 mm min.
Test method
Relationship of Mounting Distance between K8AK-PA Relays
and Ambient Temperature (Reference Values)
The following diagram shows the relationship between the mounting distances and the
ambient temperature.
If the relay is used with an ambient temperature that exceeds these values, the
temperature of the K8AK may rise and shorten the life of the internal components.