Datasheet
K8AK-AW
4
Specifications
Allowable operating voltage range 85% to 110% of power supply voltage
Allowable operating frequency range 50/60 Hz ±5 Hz
Input frequency range
K8AK-AW1 and K8AK-AW2: DC input or AC input (45 to 65 Hz)
K8AK-AW3: AC input (45 to 65 Hz)
Overload capacity
K8AK-AW1 and K8AK-AW2: Continuous input at 120% of maximum input, 1 s at 150%
K8AK-AW3: Continuous input at 120%, 30 s at 200%, and 1 s at 600% with an OMRON CT (K8AC-CT200L).
Note: CT capacity on primary side.
Repeat accuracy
Operating value ±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, DC or 50/60 Hz sine wave input)
Operating time ±50 ms (at 25°C and 65% humidity, rated power supply voltage)
Applicable stan-
dards
Conforming standards
EN 60947-5-1
Installation environment (pollution level 2, installation category III)
EMC EN 60947-5-1
Safety standards
UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No.14,
CCC: GB14048.5
Insulation resistance
20 MΩ min.
Between external terminals and case
Between power supply terminals and input terminals
Between power supply terminals and output terminals
Between input terminals and output terminals
Dielectric strength
2,000 VAC for one minute
Between external terminals and case
Between power supply terminals and input terminals
Between power supply terminals and output terminals
Between input terminals and output terminals
Noise immunity
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Vibration resistance
Frequency: 10 to 55 Hz, acceleration 50 m/s
2
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance 100 m/s
2
, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20
AW (I2 terminal)
0
10
60
50
40
30
20
51015
Distance between products d [mm]
I = 5 A
I = 3 A
I = 1 A
I = 0 A
Ambient temperature [°C]
K8AK
No.3
K8AK
No.2
K8AK
No.1
K8AK
No.4
K8AK
No.5
DIN Track Distance between products: d
Sample: K8AK-AW
Applied voltage: 240 VAC
Mounting distances: 0, 5, and 10 mm min.
Test method
●Relationship of Mounting Distance between
K8AK-AW Relays and Input Current
(Reference Values)
The following diagram shows the relationship between the mounting
distances and the input current.
If the relay is used with an input current that exceeds these values,
the temperature of the K8AK may rise and shorten the life of the
internal components.