Datasheet

K8AK-AW
2
Ratings and Specifications
Input Range
*1 The range is selected using connected terminals.
*2 The K8AK-AW3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.)
Model Range
*1
Connection
terminals
Setting range Input impedance Input type Overload capacity
K8AK-AW1
0 to 20 mA AC/DC I1-COM
2 to 20 mA AC/DC
10 to 100 mA AC/DC
50 to 500 mA AC/DC
Approx. 5 Direct input
Continuous input at
120% of maximum input.
1 s at 150%
0 to 100 mA AC/DC I2-COM Approx. 1 Direct input
0 to 500 mA AC/DC I3-COM Approx. 0.2 Direct input
K8AK-AW2
0 to 1 A AC/DC I1-COM
0.1 to 1 A AC/DC
0.5 to 5 A AC/DC
Approx. 0.12
(Load: 0.5 VA)
Direct input or
commercially
available CT
0 to 5 A AC/DC I2-COM
Approx. 0.02
(Load: 1.5 VA)
K8AK-AW3
0 to 100 A AC I2-COM
10 to 100 A AC
*2
20 to 200 A AC
*2
--- OMRON CT
Continuous input at
120% with an OMRON
CT (K8AC-CT200L).
30 s at 200%
1 s at 600%
* CT capacity on primary
side.
0 to 200 A AC I3-COM --- OMRON CT