User Manual

F03-16PE/-16PT/-15/-16PS
22
Ideal for harsh electrical room environments that are dusty and humid.
For installation in locations requiring insulated materials.
Ordering Information
Specifications
Dimensions
Sensing Band
F03-15
(Unit: mm)
Sensing Band Stickers
F03-25
(Unit: mm)
Can be used in conjunction with Sensing Bands.
Stud screw mounting requires no tools for installation.
No tools means the Sensor can be wiped clean quickly and easily.
The optional Mounting Bracket enables faster installation than
three-screw mounting.
Connect multiple Sensors to one K7L Amplifier for significant cost
savings.
Ordering Information
*1. The electrodes have a fluorine coating.
*2. Use a commercially available bonding agent for PVC. One bag
contains 10 Brackets.
*3. One bag contains 10 Blocks.
Specifications
Wiring Diagram
Any number of Sensors can be connected in parallel as long as the
following cable lengths are not exceeded for the Sensing Bands and
connecting cables.
K7L-AT50 (operate resistance of 50 MW max.): 60 m max.
K7L-U (operate resistance of 1 MW max.): 400 m max.
However, the leakage areas cannot be determined with the K7L-AT50.
Dimensions
Refer to pages 17 and 18.
Indicates models that allow free cutting.
Name Model number
Liquid Leakage Sensing Band F03-15
Sensing Band Stickers F03-25
Sheath Flexible, transparent vinyl chloride
Core SUS304 stainless steel
Ambient operating
temperature
15 to 50C
Weight Approx. 48 g (1 m)
Appearance
Structure
Appearance
Structure
F03-15
Sensing Band
8
25
Electrode pairs
Flexible, transparent
vinyl chloride
Conductors
333 (3 pairs/m)
(Stainless steel wire
0.3 mm x 12-wire braided cable)
Adhesive tape
25±2
15±1
(3)
(5)
(0.5)
(1)
Material: SUS304
Name Model number
Liquid Leakage Point Sensor
F03-16PS
F03-16PS-F
*
1
Mounting Brackets
*
2
F03-26PS
Terminal Block *3 F03-20
Material
Sensor
Amplifier
Polyethylene
Conductor Outer sheath: PVC, Inner sheath: Fluorine resin
Core
F03-16PS: SUS304 stainless steel
F03-16PS-F: SUS304 and fluorine coating
Ambient operating
temperature range
10 to 60C
Weight Approx. 30 g
Maximum number of
Point Sensors
connected per
Amplifier
You can use as many Point Sensors as required as
long as the following conditions are met.
K7L-AT50 (K7L-AT50D cannot be used): 60 m max.
K7L-U (K7L-UD cannot be used): 400 m max.
61F-GPN-V50: 200 m max.
F03-16PS
Liquid Leakage
Point Sensor
3
4
5
6
7
8
4
3
2
1
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
2
Liquid Leakage
Sensor Amplifier
K7L-AT50 or K7L-U
Terminal Block
F03-20
Liquid Leakage Point Sensor
F03-16PS
Liquid Leakage Point Sensor
F03-16PS
Sensing Band
K7L-AT50 : Total length of 60 m max. (Sensing Bands: 10 m max.)
K7L-U : Total length of 400 m max.