Datasheet

K7L-U@/-UD@
13
Model Number Legend
Note: If you want a Push-In Plus Terminal Socket, use the K7L-U@B. (The terminal
arrangement of a Push-In Plus Terminal Socket is upside down in comparison
with a Screw Terminal Socket.)
Ordering Information
*1. Accessories are available. Check the ratings for details.
*2. The applicable models of the K7L depend on the model of the
Socket. If the correct Socket is not used, the K7L nameplate will
be upside down.
Characteristics
Ratings
* For the K7L-UD.
K7L-U @ @
(1) (2)
(1) (2)
Symbol Meaning Symbol Meaning
Blank No sensor disconnection detection Blank Ivory, Screw Terminal Socket
D Sensor disconnection detection B Black, Push-In Plus Terminal Socket
Product name Model
Amplifier
Liquid Leakage Sensor
Amplifier *1
K7L-U
Liquid Leakage Sensor
Amplifier *1
K7L-UB
Liquid Leakage Sensor
Amplifier with
Disconnection Detection
Function *1
K7L-UD
Liquid Leakage Sensor
Amplifier with
Disconnection Detection
Function *1
K7L-UDB
Sensors
Sensing Band
F03-15
F03-16PE
F03-16PT
F03-16SF
F03-16SFC
Point Sensor
(for K7L-U/UB)
F03-16PS
F03-16PS-F
Mounting Brackets
and Stickers
Sensing Band Stickers
F03-25
F03-26PES
F03-26PEN
F03-26PTN
Point Sensor Mounting
Brackets
F03-26PS
Track-mounted
Socket *2
(for K7L-U/UD)
Round terminals can be
used.
P2RF-08
Round terminals cannot
be used.
P2RF-08-E
Track-mounted
Socket *2
(for K7L-UB/UDB)
Push-In Plus Terminal P2RF-08-PU
Terminal Blocks F03-20
Ambient
temperature
Operating: –10 to 55°C
Ambient humidity Operating: 45% to 85%
Insulation resistance
10 M
at 100 VDC between case and current-carrying parts
Dielectric strength
1,000 VAC at 50/60 Hz for 1 min between case and
current-carrying parts
Power consumption
1 W max.
Response time
Operate:800 ms max.
Release:800 ms max.
Startup time after power ON: 2 s max.
Weight Approx. 14 g
Rated power
supply voltage
12 to 24 VDC
(Allowable voltage fluctuation range: 10 to 30 VDC)
Operate
resistance
0 to 1 M variable
Note: The adjuster (ADJUST) on the top of the Sensor
Amplifier sets the resistance for detection within
the setting range. It is factory-set to the upper
limit. (Normally, the K7L can be used with the
adjuster at this setting.)
Disconnecti
on detection
function
*
Detection signal: 10 VDC max., 200 ms
Detection time: 10 s max.
Recovery: Operation is recovered by resetting the power supply.
Release
resistance
105% min. of operate resistance
Output
configuration
NPN open-collector transistor output with 100 mA at 30 VDC max.
for both liquid leakage detection and disconnection detection.
Note:
If the rightmost pin of the DIP switch on the side of the
Sensor Amplifier is set to the down position, the output
turns ON when liquid is detected; if it is set to the up
position, the output turns OFF when liquid is detected.
Vibration
resistance
10 to 150 Hz, 0.1-mm single amplitude with 15-m/s
2
acceleration
for 8 minutes 10 times each in X, Y, and Z directions
Shock
resistance
150 m/s
2
3 times each in six directions on 3 axes
Wiring
distance
Wiring cable
Sensing Band
Note: These values are possible on the condition that a
completely insulated 3-conductor VCT cable with
a thickness of 0.75 mm
2
and a dielectric strength
of 600 V is used together with the Liquid Sensing
Band specified by OMRON. (A 0.2-mm
2
cable
can also be used.)
Accessories
}
Total: 400 m max.
Product
Name
Terminal
Block
Screwdriver
for ADJUST
Terminator
Model F03-20 --- F03-20T
K7L-U/UB 11---
K7L-UD/
UDB
111