Datasheet
K6CM
6
Ratings and Specifications
List of Models
Ratings
Power
Supply
Power supply voltage
K6CM-@@MA: 100 to 240 VAC, 50/60 Hz
K6CM-@@MD: 24 VAC, 50/60 Hz, 24 VDC
Allowable operating voltage range 85% to 110% of power supply voltage
Power supply frequency range 45 to 65 Hz
Power consumption
K6CM-VBM@
24 VAC/24 VDC: 3.8 VA/2.1 W max.
100 to 240 VAC: 7.1 VA max.
K6CM-ISM@
24 VAC/24 VDC: 3.7 VA/2.0 W max.
100 to 240 VAC: 6.2 VA
K6CM-CIM@
24 VAC/24 VDC: 3.1 VA/1.6 W max.
100 to 240 VAC: 6.0 VA max.
Input
Vibrations
(vibration sensor)
Detection frequency 10 Hz to 10 kHz
Max. operating
acceleration
10 G
Insulation resistance
(ZCT (IRT))
Rated input voltage (Line voltage) 200 to 480 VAC, 50 Hz/60 Hz
Rated path current 300 AAC
Current,
comprehensive current
diagnosis (CT)
Rated input current 5 A, 25 A, 100 A, 200 A, 400 A, 600 A
Applicable motor type Three-phase induction motor
Outputs
Output relays Transistor output (N.C. contact)
Output relays 3-point
Output rating
Rated voltage: 24 VDC
Max. current: 50 mA, DC
Ambient operating temperature -10 to +55°C (with no condensation or icing)
Storage temperature -20 to +65°C (with no condensation or icing)
Ambient operating humidity 25% to 85% RH (with no condensation)
Storage humidity 25% to 85% RH (with no condensation)
Case color Black
Case material Polycarbonate UL94-V0
Altitude 2,000 m max.
Applicable wires Stranded wires, solid wires, or ferrules
Applicable wire size 0.25 to 1.5 mm
2
(AWG24 to 16)
Wire insertion force 8 N max. (AWG20)
Screwdriver insertion force 15 N max.
Wire stripping length 8 mm
Recommended flat-blade screwdriver XW4Z-00B (Omron)
Current capacity 10 A (per pole)
Number of insertions 50 times
Weight Approx. 200 g
Mounting
Mounts to DIN Track
screw mounting
Dimensions 45 (W) × 90 (H) × 90 (D) mm
Setting method Communication settings from a dedicated tool via EtherNet/IP
Other functions Display value selection, self-diagnosis error output, setting value initialization, operation integration
Accessories Operation manual, CD-ROM (Motor condition monitoring Tool)