Datasheet

K6CM
18
List of Parameters
Setting values
Parameter Content
Model
K6CM
-VBM
K6CM
-ISM
K6CM
-CIM
Acceleration/upper-limit alarm threshold value
(Critical and Warning)
0.00 to 9.99 G
Velocity/upper-limit alarm threshold value (Critical
and Warning)
0.00 to 45.00 mm/s
Motor temperature/upper-limit alarm threshold
value (Critical and Warning)
5 to 80°C
Temperature gap/upper-limit alarm threshold value
(Critical and Warning)
5 to 80°C
Insulation resistance/lower-limit alarm threshold
value (Critical and Warning)
0.000 to 1.000 MΩ
Degradation level/lower-limit alarm threshold value
(Critical and Warning)
0 to 999
Current/upper-limit alarm threshold value (Critical
and Warning)
10 to 100% of the rated value
Main unit IP address
Sets the IP address of the main unit.
The default value is “192.168.250.10” (common to all
models)
●●●
Software reset
Restarts the K6CM. Used to enable the settings after
changing the setting values.
0 1: Execute
●●●
MAX/MIN reset
Initializes the MAX/MIN value.
0 1: Execute
●●●
Display value type
Sets which measurement value to display in the 7-segment
display at the front of the main unit.
0: PV (Present Value), 1: MIN, 2: MAX
●●●
Trigger mode
Sets the trigger mode.
0: At all times, 1: External trigger, 2: Internal trigger
●●●
Trigger type
Sets Rise, Fall, or Level in the case of an internal trigger or
external trigger.
0: Rise, 1: Fall, 2: Level
●●●
Trigger level
Sets the trigger level when “Internal trigger” and the trigger
type “Level” have been selected.
●●●
Monitoring time
Sets the time for continuing measurement or monitoring in
the case of an internal trigger or external trigger, when the
trigger type is either Rise or Fall.
Setting value: 0.1 to 600.0 s
●●●
Alarm latch
Sets whether to enable or disable the alarm latch function.
0: Disable (no latch), 1: Enable (latched)
●●●
Use Running Time
Sets whether or not to use the main unit residual amount
function.
0: OFF (Do not use), 1: ON (Use)
●●●
Moving average times
Performs the averaging process for the past n-times of data
including the sampling data of that time, each time
sampling of the measurement value is performed.
0: OFF, 1: 2 times, 2: 4 times, 3: 8 times, 4: 16 times,
5: 32 times
●●●
Temperature unit
Sets the temperature unit.
0: °C, 1: °F
Circuit topology
Sets the Circuit topology.
0: Three-phase, three-conductor, S-phase ground
1: Three-phase, four-conductor, N-phase ground,
load-side connection
Using inverter
Sets the Using inverter.
0: OFF (without inverter), 1: ON (with inverter)
Inverter special measurement
Sets the inverter special measurement.
0: OFF, 1: ON
(Refers to the special calculation performed when the
inverter frequency and commercial frequency are close.)
Current range
Selects the connected CT
.
0: 5 A, 1: 25 A, 2: 100 A, 3: 200 A, 4: 400 A, 5: 60
0 A