Datasheet
K6CM
12
Nomenclature
Note: Warning: Indicates that it is time for maintenance.
Critical: Indicates that it is time for replacement.
* Trigger modes other than external trigger
Always: Trigger is not used. Measurement/monitoring are performed continuously after the power of the K6CM unit is turned on.
Internal trigger: Measurement/monitoring starts based on the relation between the measured value and set value (trigger level).
You can use "Trigger Type" to specify whether measurement/monitoring start and continue for a set time when the measured
value is over, or under, the set value (trigger level), or are executed while the measured value exceeds the set value (trigger
level).
Name Meaning
Alarm bar
A bar on which the color of the
emitted light changes according to
the alarm status.
It is indicated in the following colors during measurement/monitoring.
Green: Alarm status (normal)
Orange: Alarm status (Warning)
Red: Alarm status (Critical)
The alarm bar is lit out in each of the following states:
When the power is OFF, when measurement is not being performed,
and when a self-diagnosis error has occurred, etc.
Measurement type
Indicates the type of the measured
value being displayed. The type can
be switched each time the [DISP]
key is pressed on the front
operation part.
K6CM-VB “G”: Acceleration, “mm/s”: Velocity, “T”; Motor temperature,
“ T”: Temperature Gap (difference between motor
temperature and room temperature)
K6CM-IS “MΩ”: Insulation resistance, “mA”: Leakage current
K6CM-CI “Cim”: Degradation level, “A”: Current
Front
operation part
[ALM RST]
key
Releases the latched alarm state.
The main use of this key is to release the latched and fixed alarm state
after returning from the fault state to the normal state.
[DISP] key Switches the type of the measured value being displayed.
Others
If two keys are simultaneously pressed and held for 5 seconds or longer, all settings of the main unit are reset
to factory defaults.
Main unit status display
The status of the main unit is
indicated by lighting of the LCD
characters.
“MON”: Measurement / monitoring is being performed
“ERR”: A self-diagnosis error has occurred
“AGE”: Running Time notification (it is recommended to replace the
product main unit)
Transistor
output
13-14
Output of the alarm status
(Warning).
When measurement/monitoring is in progress,
OFF: Alarm state (Warning) or alarm state (Critical)
ON: Alarm state (normal)
15-16 Output of the alarm status (Critical).
When measurement / monitoring is in progress,
OFF: Alarm state (Critical)
ON: Alarm state (normal)
17-18 Self-diagnosis error output.
OFF: A self-diagnosis error has occurred
ON: Other than the above
External
trigger input
(excluding
K6CM-ISM)
3-4
Input of the external contact signal
to control measurement timing.
You can use "Trigger Type" to specify whether measurement/monitoring
continue for a set time after starting by the rise or fall of the external
contact, or are executed while the external contact is ON.
You can also specify settings to enable selection of a trigger mode other
than external trigger.
*
· Unit power supply
· External trigger input
Push-in Plus terminal
2D code
· Sensor input
Push-in Plus terminal
· Transistor output
Push-in Plus terminal
[ALM RST] key
[DISP] key
Current value, minimum value,
and maximum measurement value type
Measurement value units
(measurement type)
Alarm bar
Main unit status display
Front operation part
EtherNet/IP port
Product status display
Network status display
LCD display for measured
values and other values
Hook