Datasheet
K-10 1/32 DIN Digital Panel Meter K3GN
■ Measuring Ranges
Process Voltage/Current Inputs
No-voltage Contact/Open Collector Inputs
Digital Data Display (By RS-485 Communications)
■ Input/Output Ratings
Relay Contact Output
(Incorporating G6K Relays)
Transistor Output
■ Communications Specifications
Refer to N102 Operation Manual for more details.
Input Measuring range Measuring accuracy Input impedance Displayable range
DC voltage 1.000 to 5.000 V/
0.000 to 5.000 V
±0.1% FS ±1 digit max.
(at 23±3°C)
1 MΩ min. −19999 to 99999
(with scaling function)
−5.000 to 5.000 V ±0.1% FS ±1 digit max.
(at 23±5°C)
−10.00 to 10.00 V
DC current 4.00 to 20.00 mA/
0.00 to 20.00 mA
±0.1% FS ±1 digit max.
(at 23±3°C)
60 Ω
Input Measuring range Measuring accuracy
(at 23±5°C)
Displayable range
No-voltage contact (30 Hz max.) with ON/
OFF pulse width of 16 ms min.
0.05 to 30.00 HZ ±0.1% FS ±1 digit max. −19999 to 99999
(with scaling function)
Open collector (5 kHz max.) with ON/OFF
pulse width of 90µs min.
0 to 5000 HZ
Displayable range −19999 to 99999
Item Resistive load (cosφ = 1)
Rated load 1 A at 30 VDC
Rated carry current 1 A max. (at COM terminal)
Max. contact voltage 60 VDC
Max. contact current 1 A (at COM terminal)
Max. switching capacity 30 VA
Min. permissible load
(P level, reference value)
10 mV, 10 µA
Mechanical life 50,000,000 times min. (at a switching frequency of 36,000 times/hr)
Electrical life
(at an ambient temperature of 23°C)
100,000 times min. (at the rated load with a switching frequency of 1,800 times/hr)
Rated load voltage 24 VDC
Max. load current 50 mA
Leakage current 100 µA max.
Item RS-485
Transmission method 2-wire, half-duplex
Synchronization method Start-stop synchronization
Baud rate 1,200/2,400/4,800/9,600/19,200 bps
Transmission code ASCII
Communications Reading/Writing to
the K3GN
Read/write set values, read/write scaling values, enable/disable the writing of data through commu-
nications, forced-zero control, and other data.