Datasheet

K-10 1/32 DIN Digital Panel Meter K3GN
Measuring Ranges
Process Voltage/Current Inputs
No-voltage Contact/Open Collector Inputs
Digital Data Display (By RS-485 Communications)
Input/Output Ratings
Relay Contact Output
(Incorporating G6K Relays)
Transistor Output
Communications Specifications
Refer to N102 Operation Manual for more details.
Input Measuring range Measuring accuracy Input impedance Displayable range
DC voltage 1.000 to 5.000 V/
0.000 to 5.000 V
±0.1% FS ±1 digit max.
(at 23±3°C)
1 M min. 19999 to 99999
(with scaling function)
5.000 to 5.000 V ±0.1% FS ±1 digit max.
(at 23±5°C)
10.00 to 10.00 V
DC current 4.00 to 20.00 mA/
0.00 to 20.00 mA
±0.1% FS ±1 digit max.
(at 23±3°C)
60
Input Measuring range Measuring accuracy
(at 23±5°C)
Displayable range
No-voltage contact (30 Hz max.) with ON/
OFF pulse width of 16 ms min.
0.05 to 30.00 HZ ±0.1% FS ±1 digit max. 19999 to 99999
(with scaling function)
Open collector (5 kHz max.) with ON/OFF
pulse width of 90µs min.
0 to 5000 HZ
Displayable range 19999 to 99999
Item Resistive load (cosφ = 1)
Rated load 1 A at 30 VDC
Rated carry current 1 A max. (at COM terminal)
Max. contact voltage 60 VDC
Max. contact current 1 A (at COM terminal)
Max. switching capacity 30 VA
Min. permissible load
(P level, reference value)
10 mV, 10 µA
Mechanical life 50,000,000 times min. (at a switching frequency of 36,000 times/hr)
Electrical life
(at an ambient temperature of 23°C)
100,000 times min. (at the rated load with a switching frequency of 1,800 times/hr)
Rated load voltage 24 VDC
Max. load current 50 mA
Leakage current 100 µA max.
Item RS-485
Transmission method 2-wire, half-duplex
Synchronization method Start-stop synchronization
Baud rate 1,200/2,400/4,800/9,600/19,200 bps
Transmission code ASCII
Communications Reading/Writing to
the K3GN
Read/write set values, read/write scaling values, enable/disable the writing of data through commu-
nications, forced-zero control, and other data.