Datasheet

K-24 1/32 DIN Digital Panel Meter K3GN
Operation/Adjustment Lockouts
Prohibits key operations for operation level and adjustment level.
Initial setting is 0.
When the set value is 0 (the initial setting), protection is not set.
Setting Change Lockout
Prohibits setting changes.
The initial setting is OFF.
Note: Changes to protection level parameters, moving to advanced
function setting level, and moving to calibration level are all al-
lowed.
Initial Setting/Communications
Lockouts
Prohibits moving to the initial setting level, the communications set-
ting level, and the advanced function setting level.
The initial setting is 1.
Forced-zero shift Lockout
Prohibits the setting or clearing of a forced-zero using the front panel
key.
The initial setting is OFF.
p
p
p
p
Protect level
Setting change lockout
Prohibits setting changes using front panel keys.
Operation/adjustment
lockouts
Initial setting/communi-
cations lockouts
Forced-zero shift
lockout
Prohibits menu display, writing, etc., for
operation level and adjustment level.
Prohibits access to menu display, initial setting
level, communications setting level, and
advanced function setting level.
Prohibits use of the forced-zero function using
front panel keys.
Setting Operation level Moving to
adjustment
level
Process value
display
Set value display
0 Allowed Allowed Allowed
1 Allowed Allowed Prohibited
2 Allowed Prohibited Prohibited
Setting Meaning
OFF Setting changes using front panel keys allowed (i.e., it is
possible to move to the state where changes to settings
can be made).
ON Setting changes using front panel keys prohibited (i.e., it
is not possible to move to the state where changes to
settings can be made).
Setting Moving to initial setting
level
Moving to
communications setting
level
0 Allowed (message for mov-
ing to advanced function
setting level displayed)
Allowed
1 Allowed (message for mov-
ing to advanced function
setting level not displayed)
Allowed
2 Prohibited Prohibited
Setting Meaning
OFF Executing and clearing of forced-zero allowed.
ON Executing and clearing of forced-zero prohibited.