Datasheet

Mini Motor Contactor J7KNA 11
Cable cross-section
all connectors solid mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible with multicore cable end mm² 0.5 - 1.5 0.5 - 1.5 0.5 - 2.5
Clamps per pole 2 2 2
solid or stranded AWG 18 - 14 18 - 14 18 - 14
*1) version „VS“
*2) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): U
imp
= 8kV.
Data for other conditions on request.
*3) With reduced control voltage range 0.9 up to 1.0 x U
s
and with reduced thermal rated current I
th
to I
e
/AC15
*4) Summary switching time = release time + arc duration
*5) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used
(Varistor, RC-units, Diode units).
Mini Motor Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Typ e
J7KNA-09…
J7KNA-12…
J7KNA-09…D(VS)
*1
J7KNA-12…D(VS) J73KN-A…
Mini Contactors for North America
Data according to UL508
Main Contacts (cULus) Typ e J7KNA-09… J7KNA-12… J73KN-A…
Rated operational current "General Use" A 15 20 10
Rated operational power of three-phase motors 115V hp 2 -
at 60Hz (3ph) 200V hp 3 3 -
230V hp 3 3 -
460V hp 5 -
575V hp 10 -
Rated operational power of of AC motors 115V hp ½ ¾ -
at 60Hz (1ph) 200V hp 1 -
230V hp 2 -
Fuses A 30 30 -
Suitable for use on a capability of delivering not more than rms
(SCCR)
A 5000 5000 -
V 600 600 -
Rated voltage V AC 600 600 600
Auxiliary Contacts (cULus) heavy pilot duty AC A600 A600 A600
standard pilot duty DC Q600 Q600 Q600