Datasheet
14 Motor Contactor J7KN
Contactors
Data according to IEC 60947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type
J7KN(G)-10(D) J7KN(G)-14(D) J7KN(G)-18(D) J7KN(G)-22(D)
J7KN(G)-24 J7KN(G)-32 J7KN(G)-40 J7KN-50
Utilization category AC6a
Transformer primary switching
at inrush
Rated operational current l
e
n 3030303030303030
400V A 4,5 5,5 7,5 7,5 10,5 13,5 13,5 20
Rated operational power
dependent on inrush n
220-230V kVA 138 2,2 3 3 4,2 5,4 5,4 8
200V kVA 1,9 2,3 3,1 3,1 4,3 5,6 5,6 8,3
380-400V kVA 3,1 3,8 5,2 5,2 7,3 9,3 9,3 13,5
For different inrush-factors x
use the following formula:
Px=Pn*(n/x)
415-440V- kVA 3,4 4,2 5,7 5,7 8 10,2 10,2 15
500V kVA 3,9 4,8 6,5 6,5 9 11,5 11,5 17
660-690V kVA 5,4 6,5 9 9 12,5 16 16 24
Utilization category AC6b
Switching of three-phase capacitors
Maximum inrush current (peak value)
as multiple k of the capacitor rated
current
k
35 25 20 20 25 25 25 25
Rated operational I
e
500V A
81215,515,523323245
Rated operational power
(sin
1)
220-230V kVAr
34,5 6 68,5121217
240V kVAr
3,5 5 6,5 6,5 9,5 13 13 18,5
380-400V kVAr 5 7,5 10 10 15 20 20 29
For different multiples x
use the following formula:
Px=Pk*(k/x)
415-440V kVAr
5,5 8 11 11 16 22 22 32
500V kVAr
710131320262639
660-690V kVAr
710131320262640
Switching of reactive capacitor banks
Rated operational current l
e
690V A 8 13 18 20 28 36 42 48
Rated operational power
220-230V kVAr
2,9 5 7 7,5 11 14 16 20
240V kVAr
3,1 5,4 7 8 11 14 17 20
380-400V kVAr
5 9 12,5 13 20 25 27,5 33,3
415-440V kVAr
5,5 9,5 13 14 22 27 30 36
500VkVAr611151725303640
660-690V kVAr
815202233414855
750(850)V
kVAr
––––––––
Utilization category DC1
Switching of resistive load
Time constant L/R
1ms
Rated operational current l
e
1 pole 24V
A
20 25 32 32 50 65 80 110
60V
A
20 25 32 32 50 65 80 110
110V
A
666610101012
220V
A
0,8 0,8 0,8 0,8 1,4 1,4 1,4 1,4
3 poles in series
24V A
20 25 32 32 50 65 8/0 110
60VA 20253232506580110
110V A
20 25 32 32 50 65 80 110
220V A
16 20 20 20 30 35 35 63
Utilization category DC3 and DC5
Switching of shunt motors
and series motors
Time constant L/R
15ms
Rated operational current l
e
1 pole 24V
A
20 25 32 32 50 65 80 110
60V
A
666630303060
110V
A
1,2 1,2 1,2 1,2 1,8 1,8 1,8 1,8
220V
A
0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,25
3 poles in series
24V A
20 25 32 32 50 65 80 110
60VA 2025323240404080
110V A
20 20 20 20 40 40 40 80
220V A
2,5 2,5 2,5 2,5 4 4 4 5