Datasheet
12 Motor Contactor J7KN
Contactors
Data according to IEC 60947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type
J7KN(G)-10(D) J7KN(G)-14(D) J7KN(G)-18(D) J7KN(G)-22(D)
J7KN(G)-24 J7KN(G)-32 J7KN(G)-40 J7KN-50
Utilization category AC4
Switching of squirrel
cage motors, inching
Rated operational current I
e
open and enclosed
220VA1215181824304050
230V A 11,5 14,5 18 18 24 30 40 50
240VA1114181824324050
380-400V A 10 14 18 18 24 32 40 50
415V A 9 14 18 18 23 30 37 45
440V A 9 14 18 18 23 30 37 45
500V A 9 12 16 16 17,5 21 21 33
660-V A 7 9 9 9 17 20 20 31
690V A 6,5 8,5 8,5 8,5 17 20 20 31
1000VA––––––––
Rated operational power
of three-phase motors
50-60Hz
220-230V kW 3 4 5568,51112,5
240VkW34557911,513,5
380-400V kW 4 5,5 7,5 7,5 11 15 18,5 22
415V kW 4,5 6 8,5 8,5 12 16 20 24
440V kW 4,5 6 8,5 8,5 12 16 20 24
500V kW 5,5 7,5 10 10 15 18,5 18,5 30
660-690V kW 5,5 7,5 10 10 15 18,5 18,5 30
1000VkW––––––––
Utilization category AC5a
Switching of gas
discharge lamps
Rated operational current I
e
per pole at 220/230V
Fluorescent lamps,
uncompensated and
serial compensated
A202025254052648896
parallel compensated
A7 9 9 9 18222230
dual-connection
A22,522,5282845587298
Metal halide lamps
*1
,
*1
Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
uncompensated
A1215191930394866
parallel compensated A 7 9 9 9 18 22 22 30
Mercury-vapour lamps
*2
,
*2
High-pressure lamps
uncompensated
A22,525282845587299
parallel compensated
A7 9 9 9 18222230
Mixed light lamps
*3
*3
Blended lamps, containing a mercury high-pressureunit and a tungsten helix in a fluorescent glass bulb (daylight lamps)
A2020252540526488
Utilization category AC5b
Switching of incandescent lamps
*4
*4
Current inrush approx. 16 x l
e
Rated operational current I
e
per pole at 220/230V
A 12,5 12,5 12,5 12,5 25 31 31 43