Datasheet

10 Thermal Overload Relay J7TKN
Temperature Compensation
In case of higher ambient temperature use the following formula:
(Ambient temperature - 20) × 0.125 = correction factor in % of the
full load motor current
Example:
Ambient temperature 70°C, full load motor current 7A
(70 - 20) × 0.125 = 6.25%
Setting value: 7A + 6,25% = 7.44A
Dimensions
Data according to CULUS
Type J7TKN-A J7TKN-B J7TKN-C J7TKN-D J7TKN-E
Rated insulation voltage V~ 600 600 600 600 600
Rated current A2332427485
Auxiliary contacts
Rated voltage
same potential V AC 600 600 600 600 600
different potential V~ 150 150 150 150 150
Switching capacity AC VA 500 500 600 600 600
of aux. contacts A42444
J7KNA-09 + J7TKN-A(A)
J7KNA-12
J7KN-10D + J7TKN-AB
J7KN-14D
J7KN-18D
J7KN-22D
J7KNG-10 + J7TKN-AB
J7KNG-14
J7KNG-18
J7KNG-22
J7KN-10D + J7TKN-B
J7KN-14D
J7KN-18D
J7KN-22D