Datasheet

Tachometer H7CX-R 45
Characteristics
Note: 1. To meet UL listing requirements with the H7CX-R11@ models, an OMRON P2CF-11-@ or P3GA-11 Socket must be mounted on the H7CX. Otherwise,
H7CX-R11@ models are considered to meet UL508 recognition requirements.
2. The Y92S-29 Waterproof Packing and Y92F-30 Flush Mounting Adapter are necessary to ensure IP66, NEMA4, and UL Type 4X waterproofing between the
H7CX and installation panel.
Life-test Curve (Reference Values)
Resistive Load Inductive Load
Reference: A current of 0.15 A max. can be switched at 125 VDC (cosφ=1) and current of 0.1 A max. can be switched if L/R=7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
Inrush Current (Reference Values)
Item H7CX-R
Insulation resistance 100 M
min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and between non-con-
tinuous contacts
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC (for 100 to 240 VAC), 50/60 Hz for 1 min between power supply and input circuit (1,000 VAC for 24 VAC/12 to 24 VDC)
2,000 VAC 50/60 Hz for 1 min between control output, power supply, and input circuit
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage 3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC,
1.5 kV for 24 VAC/12 to 24 VDC
Noise immunity
±1.5 kV (between power terminals)
±600 V (between input terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1
µs, 1-ns rise)
Static immunity Destruction: 15 kV
Malfunction: 8 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude, each in three directions four cycles (8 min per cycle)
Malfunction: 10 to 55 Hz with 0.35-mm single amplitude, each in three directions four cycles (8 min per cycle)
Shock resistance
Destruction: 294 m/s
2
each in three directions
Malfunction: 98 m/s
2
each in three directions
Life expectancy Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load)
See Life-test Curve (Reference Values) on page 45.
Approved safety standards
(See notes 1 and 2.)
UL508/Listing, UL 50 Type 4X for indoor use (enclosure rating)
CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
EMC (EMI) EN61326
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61326
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2);
8 kV air discharge (level 3)
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz
±5 MHz) (level 3)
Immunity Conducted Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 2);
2 kV line to ground (power and output lines) (level 3)
Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Degree of protection Panel surface: IP66, NEMA 4 (indoors), and UL Type 4X (indoors) (See note 2.)
Weight Approx. 140 g
1,000
700
500
300
100
70
50
01 2 3
4
250 VAC (cosφ=1)
Load current (A)
30 VDC (cosφ=1)
No. of operations (×10
3
)
1,000
700
500
300
100
70
50
01 2 3
4
250 VAC cosφ=0.4
Load current (A)
30 VDC (L/R=7 ms)
No. of operations (×10
3
)
Model Voltage Applied voltage Inrush current (peak value) Time
H7CX-R11 100 to 240 VAC 264 VAC 5.8 A 0.7 ms
H7CX-R11D1 24 VAC/12 to 24 VDC 26.4 VAC 10.4 A 1.2 ms