Multifunction Preset Counter H7CX-A (Tachometer Function) 33
Output Allocation (otst)
When using H7CX-AU@ models as 2-stage counter, each output can
be flexibly allocated to either stage 1 or 2.
Transistor output placed for SV1 and contact output for SV2 or vice
verse, as in the following table.
H7CX-AU/-AUD1
H7CX-AUSD1
Key Protect Level (kypt)
Set the key protect level.
When the key-protect switch is set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the key-
protect switch after the H7CX is mounted to the panel.
Note: Changing mode to configuration selection mode ( + 1 s min.) or function setting mode ( 3 s min.).
OUT1 OUT2
off
Transistor (12-13) Contact (3, 4, 5)
on
Contact (3, 4, 5) Transistor (12-13)
OUT1 OUT2
off
Transistor (12-13) Transistor with diode
(3, 4, 5)
on
Transistor with diode
(3, 4, 5)
Transistor (12-13)
ON
OFF
Note: Factory-set to OFF
Key protect indicator
(See note)
Level Meaning Details
Changing mode
(See note.)
Switching display
during operation
Reset key Up/down key (Up key for
6-digit models)
KP-1 (default setting) No Yes Yes Yes
KP-2 No Yes No Yes
KP-3 No Yes Yes No
KP-4 No Yes No No
KP-5 No No No No