Explanation of Functions
Absolute value setting/forecast value setting 
(setm)
Set value 1 can be set as the forecast value setting (ofst) or the 
absolute value setting (
abs). 
Forecast Value Setting
• OUT1 (forecast output) turns ON when the present value reaches 
the forecast value.
Forecast value = Set value - Forecast set value
Note: The forecast set value is used to set the deviation for the set value.
• OUT2 (control output) turns ON when the present value reaches 
the set value.
• If the forecast set value ≥ set value, OUT1 (forecast output) will turn 
ON as soon as timing starts.
Absolute Value Setting
• OUT1 (control output 1) turns ON when the present value reaches 
set value 1.
• OUT2 (control output 2) turns ON when the present value reaches 
set value 2.
Refer to pages 18 and 28 for information on other functions.
Self-diagnostic Function
The following displays will appear if an error occurs.
*1. This includes times when the life of the EEPROM has expired.
*2. The normal display and 
e3
 will appear alternately.
When the Reset Key is pressed, 
e3
 will no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the Timer will 
continue without clearing the output ON count.)
Set
 value
Forecast
 value
Forecast
set value
0
Forecast output
 (OUT1)
Control output
 (OUT 2)
Present 
value 
Example: F-1 Mode
Set value 2
Set value 1
0
Control output 1
 (OUT1)
Control output 2
 (OUT2)
Present 
value
Example: F-1 Mode
Main display Sub-display Error Output status Correction method  Set value after reset
e1
Not lit CPU  OFF
Either press the Reset Key or 
reset the power supply. 
No change
e2
Not lit Memory error (RAM)  OFF Reset the power supply.  No change
e2 sum
Memory error EEPROM 
*1
  OFF Reset Key.  Factory setting
 e3 
*2
No change 
Output ON count alarm set 
value exceeded
No change  Reset Key  No change