Datasheet

H5CX-A@-N/-L@-N
32
Key Protect Level
When the key-protect switch is set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-7).
The key protect indicator is lit while the key-protect switch is set to ON.
* Changing mode to Timer/Twin Timer Selection Mode or Function Setting Mode.
Self-diagnostic Function
The following displays will appear if an error occurs.
*1. This includes times when the life of the EEPROM has expired.
*2. The normal display and
e3
will appear alternately.
When the Reset Key is pressed,
e3
will no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the Timer will
continue without clearing the output ON count.)
Level Meaning
Details
Changing mode*
Switching display
during operation
Reset Key
Up/down key
KP-1
(default setting)
Invalid Valid Valid Valid
KP-2 Invalid Valid Invalid Valid
KP-3 Invalid Valid Valid Invalid
KP-4 Invalid Valid Invalid Invalid
KP-5 Invalid Invalid Invalid Invalid
KP-6 Invalid Invalid Valid Valid
KP-7 Invalid Invalid Invalid Valid
Main display Sub-display Error Output status Correction method Set value after reset
e1
Not lit CPU OFF
Either press the reset key or
reset the power supply.
No change
e2
Not lit Memory error (RAM) OFF Reset the power supply. No change
e2 sum
Memory error EEPROM
*1
OFF Reset Key Factory setting
e3
*2
No change
Output ON count alarm set
value exceeded
No change Reset Key No change
* Factory-set to OFF
*
OFF
(Disabled)
ON
(Enabled)
Key protect indicator