H5CX-A@-N/-L@-N
29
Twin Timer
Timing Charts
Operating Procedures for Timer Function
Models without Instantaneous Contact Outputs
The gate input is not included in the H5CX-L8@ models.
Mode toff: Flicker OFF start 1 (Timer resets when power comes ON.) 
Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. 
The status of the control output is reversed when time is 
up (OFF at start). 
While the start signal is ON, the timer starts when the 
power comes ON or when the reset input goes OFF. 
Note: Normal output operation will not be possible if 
the set time is too short.
Set the value to at least 100 ms (contact output 
type).
Mode ton: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. 
The status of the control output is reversed when time is 
up (ON at start). 
While the start signal is ON, the timer starts when the 
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if 
the set time is too short. 
Set the value to at least 100 ms (contact output 
type). 
Mode toff-1: Flicker OFF start 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation 
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. 
The status of the control output is reversed when time is 
up (OFF at start). 
While the start signal is ON, the timer starts when the 
power comes ON or when the reset input goes OFF. 
Note: Normal output operation will not be possible if 
the set time is too short.
Set the value to at least 100 ms (contact output 
type). 
Power
Output
*
Start signal
 input
Timing 
OFF
Timing 
ON
Timing 
OFF
Timing 
ON
ON time
OFF time
0
OFF time
ON time
0
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Power
Output
*
Start signal
 input
Timing 
ON
Timing 
OFF
Timing 
ON
Timing 
OFF
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Power
Output
*
Start signal
 input
Timing 
OFF
Timing 
ON
Timing 
OFF
(a + b = ON time)
a b
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram