Datasheet

H5CX-A@-N/-L@-N
22
Timer
Mode d: Signal OFF delay (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is enabled during timing.
The control output is ON when the start signal is ON
(except when the power is OFF or the reset is ON).
The timer resets when the time is up.
Note: Output functions only during start signal input
when setting is 0.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is enabled during timing.
Timing starts when the start signal comes ON.
The timer resets when the time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Output is disabled when the setting is 0.
Mode F: Cumulative (Timer does not reset when power comes ON.)
Basic operation Detailed operation
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
Note: Output is instantaneous when setting is 0.
When the H5CX is used with power start, there will be a
timer error (approximately 100 ms each time the H5CX
is turned ON) due to the characteristics of the internal
circuitry. Use the H5CX with signal start if timer
accuracy is required.
Mode Z: ON/OFF-duty-adjustable flicker (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when power
comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Output
*
Start signal
input
Timing
Power
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
input
Timing
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Start signal
input
Timing
Sustained
Timing
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
input
Timing
(cycle time)
Timing
ON duty
(%)
Timing
(cycle time)
Timing
ON duty
(%)
Power
Start signal
Gate
Reset
Control output
Cycle time
ON duty setting
(%) ON time
0
Cycle time
ON duty setting
(%) ON time
UP
DOWN
0
Timing diagram