Datasheet
B-40 Solid-state Two-wired Timer H3DS-X
Specifications
■ General
Note: Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
■ Time Ranges
Note: When the time setting dial is set to “0” for any time scale, the output will operate instantaneously.
■ Ratings
Note: The ripple in DC power supply must be 5% max.
Item H3DS-X
Operating mode ON-delay
Operating/Reset method Time-limit operation/self-resetting
Output type SCR output
External connections Screw terminal, Screw-Less Clamp
Terminal block
Screw terminal type: Clamps two 2.5-mm
2
max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm
2
max. bar terminals without sleeves.
Terminal screw tightening torque 0.98 N·m max.
Mounting method DIN track mounting (see note)
Attachment Nameplate label
Approved standards UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100
Time scale display Time range
0.1 s 0.1 to 1.2 s
1 s 1 to 12 s
0.1 m 0.1 to 1.2 min
1 m 1 to 12 min
0.1 h 0.1 to 1.2 h
1 h 1 to 12 h
10 h 10 to 120 h
Rated supply voltage (see note) 24 to 230 VAC/VDC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-off time: 0.1 s
Reset voltage 1.0 VAC/VDC max.
Reset current 5 mA max.
Power consumption 5 mA max.
Control output SCR output:5 mA to 0.7 A
Ambient temperature Operating: –10°C to 55°C (with no icing)
Storage: –25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%