Solid-state Timer Timers H3DS DIN Track Mounted, Standard 17.5-mm Width Timer Range • A wide AC/DC power supply range (24 to 230 VAC/ 24 to 48 VDC) reduces the number of timer models kept in stock. (24 to 230 VAC/VDC with H3DS-XL@) • Smart Dial/Selector-locking Mechanism: Prevents the dials and selectors on the Timer’s front panel from being inadvertently operated or being operated without authorization. The lock can only be unlocked and locked with an optional pen-type Lock Key.
B-10 Solid-state Timer H3DS
Solid-state Multi-functional Timer Timers H3DS-M/-S/-A • Eight operating modes (H3DS-M) and four operating modes (H3DS-S) cover a wide range of applications. • A wide time setting range of 0.10 s to 120 h. • Two LEDs indicate power and relay status respectively. Model Number Structure ■ Model Number Legend H3DS - L 1 1. 2. 3.
■ Accessories (Order Separately) Lock Key Y92S-38 Mounting Track 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.
Specifications Item H3DS-ML@ H3DS-SL@ ON-delay (Signal or Power) Flicker OFF start (Signal or Power) Flicker ON start (Signal or Power) Signal ON/OFF-delay Signal OFF-delay Interval (Signal or Power) Signal ON/OFF-delay One-shot (Signal or Power) A: B2: E: J: ON-delay Flicker ON start Interval One-shot Timers ■ General H3DS-AL@ A: ON-delay (fixed) Operating mode A: B: B2: C: D: E: G: J: Input type Voltage input Output type Relay: SPDT External connections Screw terminal, Screw-Less Clamp Ter
■ Characteristics Accuracy of operating time ±1% max. of FS (±1% ±10 ms max. at 1.2-s range) Setting error ±10% ±50 ms max. of FS Signal input time 50 ms min. Influence of voltage ±0.7% max. of FS (±0.7% ±10 ms max. at 1.2-s range) Influence of temperature ±5% max. of FS (±5%±10 ms max. at 1.2-s range) Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min.
Connections Timers ■ Block Diagram H3DS-ML@ AC (DC) input Zero setting detection circuit Time scale/ unit selectors Operating mode selector Oscillation circuit Counting circuit Output circuit Input circuit Indicator circuit Power supply circuit Start input Power-ON Output indicator indicator H3DS-SL@/-AL@ AC (DC) input Power supply circuit Zero setting detection circuit Time scale/ unit selectors Operating mode selector Oscillation circuit Counting circuit Output circuit Indicator circu
■ Terminal Arrangement H3DS-MLC A1 15 H3DS-ML H3DS-SLC/-ALC B1 A1 A1 15 H3DS-SL/-AL 15 B1 A1 15 L 15 15 18 18 16 16 15 18 16 18 16 18 15 16 A2 A2 18 (see note 1) 16 18 16 18 16 A2 A2 (DIN notation) (see note 1) (DIN notation) Note: 1. DC supply voltage does not require the designation of polarity. 2. The contact symbol for the H3DS is indicated with contact for conventional timers.
■ Basic Operation Setting of Selector The selectors can be turned clockwise and counterclockwise to select the desired time scale, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting.
■ Timing Chart Note: 1. The minimum power reset time is 0.1 s and the minimum signal input time is 0.05 s. 2. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set. 3. There is no start input for H3DS-SL@/-AL@ models. Operation starts at power-on.
Operating mode Timing chart D: Signal OFF-delay t–a t–a t t–a Timers t Power (A1 and A2) Basic operation Start (B1 and A2) (see note) Power Output relay: NC 15 and 16 * Start t Output relay: NO (output indicator) 15 and 18 Output * Start input is valid and re-triggerable while the Timer is in operation.
Nomenclature H3DS-ML@/-SL@ H3DS-MLC/-SLC Wire connection holes Output indicator (orange) (Lit while Timer output is ON.) Time setting dial (set time) Set time window Lock for time setting dial Time scale display window and selector (select one from 1 s, 0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m, and 0.
Dimensions Timers Note: All units are in millimeters unless otherwise indicated. H3DS-ML/-SL/-AL Surface color: Light gray 5Y7/1 (OMRON) H3DS-MLC/-SLC/-ALC 17.
B-22 Solid-state Multi-functional Timer H3DS-M/-S/-A
Solid-state Twin Timer Timers H3DS-F • Operates in flicker-OFF or flicker-ON start mode with one Unit. • Independent ON- and OFF-time settings. Combinations of long ON- or OFF-time and short OFF- or ONtime setting are possible. • Long time range from 0.1 s to 12 h for both ON and OFF time settings. Model Number Structure ■ Model Number Legend H3DS -F L 1 2 3 1. F: Twin timers 2. L: Smart lock mechanism 3.
Specifications ■ General Item H3DS-F Operating mode Flicker-OFF/Flicker-ON start Output type Relay: SPDT External connections Screw terminal, Screw-Less Clamp Terminal block Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves. Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. Terminal screw tightening torque 0.98 N·m max. Mounting method DIN track mounting (see note) Attachment Nameplate label Approved standards UL508, CSA C22.2 No.
Accuracy of operating time ±1% max. of FS (±1% ±10 ms max. at 1.2-s range) Setting error ±10% ± 50 ms max. of FS Timers ■ Characteristics Influence of voltage ±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range) Influence of temperature ±5% max. of FS (±5% ± 10 ms max. at 1.2-s range) Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1 min.
Connections ■ Block Diagram ON indicator (Orange) AC (DC) input OFF indicator (Green) ON/OFF start selector Indicator circuit Time scale selector ROM RAM Clock One-chip microcomputer Power supply circuit Output circuit ■ I/O Function Inputs Outputs Flicker-ON start operation begins when inputs are turned ON. Control output Outputs are turned ON/OFF according to the time set by the ON-and OFF-time setting dial.
Operation Timers ■ Basic Operation Setting of Selector Time Setting The selectors can be turned clockwise and counterclockwise to select the desired time scale, or operating mode. Use the ON/OFF-time setting dials to set the ON/OFF time. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting.
Nomenclature H3DS-FL@ H3DS-FLC Wire connection holes Output ON/OFF indicator When the output is ON: Orange When the output is OFF: Green ON-time display window ON-time setting dial Lock for ON-time setting dial ON-time scale display window and selector (select one from 0.1 s, 1 s, 0.1 m, 1 m, 0.1 h, and 1 h) OFF-time display window Lock for ON-time scale selector OFF-time scale display window and selector (select one from 0.1 s, 1 s, 0.1 m, 1 m, 0.
Dimensions Timers H3DS-FL Surface color: Light gray 5Y7/1 (OMRON) 17.5 73 45 80 44 68 H3DS-FLC Surface color: Light gray 5Y7/1 (OMRON) 73 17.
B-30 Solid-state Twin Timer H3DS-F
Solid-state Star-delta Timer Timers H3DS-G • A wide star-time range (up to 120 seconds) and star-delta transfer time range (up to 1 second) Model Number Structure ■ Model Number Legend H3DS -G L 1 2 3 1. G: Star-delta timer 2. L: Smart lock mechanism 3.
Specifications ■ General Item H3DS-G Operating mode Star-delta operation Operating/Reset method Time-limit operation/Self-reset External connections Screw terminal, Screw-Less Clamp Terminal block Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves. Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. Terminal screw tightening torque 0.98 N·m max.
■ Characteristics ±1% max. of FS Setting error ±10% ± 50 ms max. of FS Total tolerance of transfer time ± (25% FS + 5 ms) max. Influence of voltage ±0.5% max. of FS Influence of temperature ±5% max. of FS Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1 min. Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Connections ■ Block Diagram Star operation time scale selector Star-delta transfer time selection Star operation time counting circuit Star-delta transfer time oscillation circuit AC (DC) input Power supply circuit Star operation time oscillation circuit Star-delta transfer time counting circuit Star operation Output circuit Delta operation Indicator circuit Star operation Delta operation indicator indicator ■ I/O Functions Inputs Outputs --Control output Star output is turned OFF when the dial
Operation Timers ■ Basic Operation Setting of Selector Time Setting The selectors can be turned clockwise and counterclockwise to select the desired time scale, or operating mode. The star operation time of the Timer is set with the time setting dial. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting.
Nomenclature H3DS-GL@ H3DS-GLC Wire connection holes Delta operation indicator (orange) Set time window Time setting dial (for setting star operation time) Star-delta transfer time and star operation time scale display window and selector Lock for time setting dial Release holes Lock for star-delta transfer time and star operation time scale Star operation indicator (green) 18 28 A2 Wire connection holes (Front View) (Front View) Attach the enclosed label here as a nameplate.
Dimensions Timers H3DS-GL Surface color: Light gray 5Y7/1 (OMRON) 17.5 73 80 45 44 68 H3DS-GLC Surface color: Light gray 5Y7/1 (OMRON) 17.
B-38 Solid-state Star-delta Timer H3DS-G
Solid-state Two-wired Timer Timers H3DS-X • Covers wide range of supply voltage (24 to 230 VAC/VDC). Model Number Structure ■ Model Number Legend H3DS -X L 1 2 3 1. X: Two-wired timer 2. L: Smart lock mechanism 3.
Specifications ■ General Item H3DS-X Operating mode ON-delay Operating/Reset method Time-limit operation/self-resetting Output type SCR output External connections Screw terminal, Screw-Less Clamp Terminal block Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves. Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. Terminal screw tightening torque 0.98 N·m max.
■ Characteristics ±1% max. of FS (±1% ±10 ms max. at 1.2-s range) Setting error ±10% ± 50 ms max. of FS Reset time 0.1 s max. Influence of voltage ±0.5% max. of FS (±0.5%±10 ms max. at 1.2-s range) Influence of temperature ±5% max. of FS (±5%±10 ms max. at 1.2-s range) Insulation resistance 100 MΩ min.
■ Terminal Arrangement H3DS-XLC H3DS-XL A1 A1 A2 A2 Note: DC supply voltage does not require the designation of polarity. Operation ■ Basic Operation Setting of Selector The selectors can be turned clockwise and counterclockwise to select the desired time scale, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured.
■ Timing Charts Timers Rt 0.1 s min. Power (A1 and A2) Output ON Indicator OFF Set time Rt: Resetting time Nomenclature H3DS-XL@ H3DS-XLC Wire connection holes Set time window Time setting dial (set time) Lock for time setting dial Time scale display window and selector (select one from 1 s, 0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m, and 0.1 m) Release holes Lock for time scale selector H3DS-XL A2 Power-ON indicator (green) (Lit while the power is ON.
Dimensions H3DS-XL Surface color: Light gray 5Y7/1 (OMRON) H3DS-XLC 17.
Installation of Screw-Less Clamp Models Timers ■ Tools A flat-blade screwdriver should be used to mount the cables. Applicable Screwdriver ● Flat-blade, Parallel-tip, 2.5 mm diameter • Flat-blade, Parallel-tip 2.5 dia. • Flat-blade, Flared-tip Cannot be used. Examples: FACOM AEF.2.5 × 75E VESSEL No. 9900-(-)2.5 × 75 WAGO 210-119 WIHA 260/2.5 × 40 ■ Applicable Wires Applicable Wire Sizes 0.2 to 1.
■ Wiring ■ Precautions Use wires of the applicable sizes specified above. The length of the exposed conductor should be 6 to 7 mm. Always insert the screwdriver straight into the hole, never at an angle. The clamp spring may be deformed if the screwdriver is not straight. 6 to 7 mm Fig. 1 Exposed Conductor Length Use the following wiring procedure. 1. Insert the specified screwdriver into the release hole located beside the wire connection hole where the wire is to be inserted.
Accessories (Order Separately) Timers Note: All units are in millimeters unless otherwise indicated. ■ Dimensions Lock Key Y92S-38 6.4 100 Mounting Track PFP-100N, PFP-50N PFP-100N2 16 7.3±0.15 4.5 4.5 35±0.3 15 25 25 10 25 1,000 (500) (see note) 25 10 35±0.3 27 27±0.15 15 1 15 (5) (see note) 25 25 25 10 1,000 25 15 10 24 29.2 1 1.5 Note: The values shown in parentheses are for the PFP-50N. Spacer PFP-S End Plate PFP-M 10 6.2 16 12 5 1.8 1 35.5 35.5 50 1.8 11.
Precautions ■ Changing of Setting ■ Power Supplies The H3DS Series is provided with a transformerless power supply system. An electric shock may be received if the input terminal is touched while power is being supplied. Use the bar terminal for wiring the H3DS. Using a stranded-wire terminal may cause a short-circuit due to a stray wire entering into the Timer. Both AC and DC power supplies can be connected to the power input terminals without regarding polarity.
The H3DS as a built-in timer conforms to EN61812-1 provided that the following conditions are satisfied: Contact or transistor for external input signal A1 Incorrect ■ Precautions for EN61812-1 Conformance B1 H3DS-ML@ Power supply The output section of the H3DS is provided only with basic isolation. To ensure reinforced isolation required by the EN61812-1, provide supplementary basic isolation on the load side connected to the output.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. L098-E1-05 B-50 In the interest of product improvement, specifications are subject to change without notice.