Datasheet

H3DK-G
20
Operating Procedures
Basic Operation
Setting the Delta Time Range and the Star-delta Transfer
Time (t2)
Star Time (t1) Range
Set the star-delta transfer time.
For ×1 (1 to 12 s), use side (A) (labeled “t1×1”).
For ×10 (10 to 120 s), use side (B) (labeled “t10×1”).
(See following diagram.)
Setting the Time
The start time is set with the main dial.
Timing Chart
Setting the Time Ranges
t2t2
0.5s
0.25s
0.1s
0.05s
0.5s
0.25s
0.1s
0.05s
t1x10t1x1
(A) (B)
Star-delta transfer
time setting (t2)
Switches the start
time (t1) range.
Setting the Time
Main dial
Note: “t1” is the start set time. “t2” is the transfer time.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
t
1
t2
t1: Star time setting
t
2: Transfer time
Power (A1 and A2)
Star contacts (15 and 18)
Delta contacts (25 and 26)
0.5 s min.
Star operation indicator
Delta operation indicator