Datasheet
G7SA
5
Options (order separately)
Sockets
*1. When operating the P7SA-@F-ND-PU at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.25 A
for each degree above 50°C.
When operating the P7SA-@F-ND at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.3 A for
each degree above 50°C.
When operating the P7SA-@F at a temperature between 50 and 85°C, reduce the continuous current (6 A at 50°C or less) by 0.1 A for each
degree above 50°C.
*2. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
Short Bars (for P7SA-@F-ND-PU)
Certified Standards
Safety Relay Unit
EN Standards, VDE Certified
UL Standards Certification (File No. E41515) Industrial Control Devices
CSA standard CSA C22.2 No.14 Industrial Control Devices
Push-In Plus terminals Screw terminals PCB terminals
4 poles 6 poles 4 poles 6 poles 4 poles 6 poles
Items Models
P7SA-10F-ND-PU P7SA-14F-ND-PU
P7SA-10F(-ND) P7SA-14F(-ND) P7SA-10P P7SA-14P
Ambient operating temperature
• With operation indicator LED/built-in diode
P7SA-@F-ND(-PU): −20 to +70°C
• Without operation indicator LED/built-in diode
P7SA-@F: −40 to +85°C
(with no icing or condensation)
−40 to +85°C
(with no icing or condensation)
Ambient operating humidity 25% to 85% 5% to 85%
Continuous carry current 6 A *1
Dielectric
strength
Between coil and
contact terminals
4,000 VAC for 1 min.
2,500 VAC for 1 min.
Between contact
terminals of different
polarity
2,500 VAC for 1 min.
Between contact
terminals of same
polarity
1,500 VAC for 1 min.
Insulation resistance 1,000 MΩ min. *2
Weight Approx. 58 g Approx. 70 g Approx. 44 g Approx. 59 g Approx. 9 g Approx. 10 g
Application Applicable sockets Models Maximum carry current
Ambient operating
temperature
Ambient operating
humidity
Crossover wiring of
contact terminals
(bottom)
P7SA-@F-ND-PU
XW5S-P2.5-2@
24 A −40 to 55°C 5% to 95%
XW5S-P2.5-3@
XW5S-P2.5-4@
XW5S-P2.5-5@
Models
Ratings Standard number Certification No. Operating coil Contact ratings
G7SA-2A2B
12, 18, 21, 24, 48,
110 VDC
EN/IEC 61810-1
Electromagnetic relay
EN/IEC 61810-3
Relays with forcibly guided
contacts
125547
12, 18, 21, 24, 48,
110 VDC
6 A, 240 VAC (Resistive)
6 A, 30 VDC (Resistive)
G7SA-3A1B
G7SA-3A3B
G7SA-4A2B
G7SA-5A1B
Models
Standard number Category Listed/Recognized Contact ratings Operating Coil ratings
G7SA-2A2B
UL508 E41515 Recognized
6 A, 250 VAC (Resistive)
6 A, 30 VDC (Resistive)
12, 18, 21, 24, 48,
110 VDC
G7SA-3A1B
G7SA-3A3B
G7SA-4A2B
G7SA-5A1B
Models
Class number File No. Contact ratings Operating Coil ratings
G7SA-2A2B
3211-07 LR35535
6 A, 250 VAC (Resistive)
6 A, 30 VDC (Resistive)
12, 18, 21, 24, 48,
110 VDC
G7SA-3A1B
G7SA-4A2B
G7SA-5A1B