Datasheet
2 Slim Relay G2RV
Specifications
■ Input Ratings
■ Contact Ratings
Note: P level: λ
60
= 0.1 x 10
-6
/operation
Rated voltage Rated current Operate voltage Release voltage Power consumption Input voltage
AC DC % of rated voltage AC (VA)
Approx.
DC (mW)
Approx.
% of rated voltage
50 Hz 60 Hz
12 VDC --- --- 27.2 80% 10% --- 300 mW ±10%
24 VDC --- --- 13.3 --- 300 mW
24 VAC/DC 21.1 22.5 13.0 0.5 VA 300 mW
48 VAC/DC 8.5 9.0 5.2 0.4 VA 250 mW
110 VAC 7.1 7.5 --- 0.8 VA ---
230 VAC 7.3 7.9 --- 1.7 VA ---
Number of poles 1 pole
Load Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Rated load 6 A at 250 VAC;
6 A at 30 VDC
2.5 A at 250 VAC;
2 A at 30 VDC
Rated carry current 6 A
Max. switching voltage 400 VAC, 125 VDC
Max. switching current 6 A
Max. switching power 1,500 VA
180 W
500 VA
60 W
Failure rate (reference value) 10mA at 5VDC (P level)