Datasheet
F3S-TGR-N_M / F3S-TGR-N_U
3
Specifications
Electrical Data
Mechanical Data
Reliability Data
F3S-TGR-N_PM F3S-TGR-N_PU
Technology RFID (Code) and hall sensing (Distance check)
Serial switching up to 20 pcs. in series
Code
Master coded:
Every switch same code
*1
*1
Re-teach needed if exchange of actuator: Power down - replace the actuator and close the door or bring the new actuator close to the sensor - power up
Unique coded:
32 × 10
6
different codes
Indicator
LED lighted - Indication of safety circuit closed - Door close
LED dark - Indication of safety circuit opened - Door open
Power supply 24 VDC ±10%
Power consumption Max. 30 mA @ 24 VDC
Minimum switched current 10 VDC, 1 mA
Rated insulating voltage 250 VAC
Insulation Resistance 100 M
Output Types Safety Channel 1 NC
Safety Channel 2 NC
Auxiliary Channel NO
200 mA, max. 24 VDC, Solid State
Switching frequency Max. 1.0 Hz
Contact release time <2 ms
Actuator approach speed
Min. 4 mm/s
Max. 1000 mm/s
Initial contact resistance <500 m
Body Material Polyester
Mounting Position
(under attention to the precautions)
Any direction
Recommended mounting gap 5mm
Tolerance to misalignment 5 mm in any direction from 5 mm setting gap
Operating distance
OFF ON (Sao) 10 mm
ON OFF (Sar) 20 mm
Temperature Range –25… +80°C
Enclosure Protection
Flying lead IP69K
M12 connector IP67
Cable material
Flying lead PVC, 8 core, Ø 6 mm o.d.
M12 connector 250 mm, PVC, Ø 6 mm o.d.
Mounting Bolts 2 × M4
Tightening Torque for Mounting Bolts 1Nm
Shock Resistance (IEC 68-2-27) 11 ms, 30 g
Vibration Resistance (IEC 68-2-6) 10… 55 Hz, 1 mm
Performance Level (EN ISO 13849-1) PLe (If both channels are used in combination with a PLe control device)
Category Cat4
MTTFd 1100 a
Diagnostic Coverage DC 99% (high)
Safety Integrity Level (EN 62061) SIL3 (If both channels are used in combination with a SIL3 control device)
Standards
EN1088, EN 60947-5-3, EN 60204-1, UL508
EN ISO 14119
EN ISO12100
EN ISO 13849-1
EN 62061