Datasheet
E8PC
26
Ratings and Specifications
Sensors
Model
PNP(COM2) E8PC-010D-E E8PC-100D-E E8PC-400D-E
PNP(COM3) E8PC-010T-E E8PC-100T-E E8PC-400T-E
NPN E8PC-010-E E8PC-100-E E8PC-400-E
Pressure
monitoring
*1
Rated pressure range -0.1 to 1 MPa 0 to 10 MPa 0 to 40 MPa
Display range -0.20 to 1.10 MPa -0.10 to 11.00 MPa -0.10 to 44.00 MPa
Withstand pressure *2 4 MPa 30 MPa 50 MPa
Burst pressure 8 MPa 60 MPa 80 MPa
Display resolution 0.001 MPa 0.01 MPa 0.01 MPa
Applicable fluid
temperature
*3
-20 to +100°C (no icing or condensation)
Pressure response time
*4
Control output: Select 3 to 6000 ms
Analog output: Set value + 2 ms (90% response)
Pressure monitoring
precision
±1.0% of F.S. or less
Pressure repeatability *5 ±0.3% of F.S. or less
Ambient temperature
characteristics
*6
±0.6% of F.S./10°C
Hysteresis Variable
Pressure type Gauge pressure
Temperature
monitoring
*7
Temperature monitoring
rated range
-20 to 100°C
Temperature monitoring
precision
±4°C
Temperature repeatability ±1°C
Control output
judgment
(selectable)
Standard mode Judge if the measured value is the threshold value or more (or less).
Window mode Judge if the measured value is within the upper and lower limits.
Compatible fluid
Gas and fluid not corroding the material of the wetted part (such as water, glycol solution, and
oil)
Display method
Numerical value indication: 4-digit 7-segment white LED with inverting function
Status indicator: Normal operation (green), status indication (orange), and error
(red) The content of status indication is selectable.
Output indicator: OUT1 operation (orange), OUT2 operation (orange)
Unit indication: E8PC-@@@@: MPa (white),
E8PC-@@@@-E: MPa (white), bar (white), psi (white), °C (white)
IO-Link indicator: Lighting when communications are in progress (green)
Delay setting
1 to 9999 ms
(Select a function from invalid, ON delay, OFF delay, and one-shot.)
Connection method M12, 4-pole connector type
Connecting diameter G3/4 male (Use the optional adapter to convert the diameter) Connection strength 20 N·m
Output ch1
(selectable)
Control output
Pressure control output (N.O./N.C.)
E8PC-@@@D/T: PNP
E8PC-@@: NPN
30 VDC or less, Class 2, max. 100 mA, residual voltage 1 V or less
Output ch2
(selectable)
Control output
Pressure control output (N.O./N.C.) / temperature control output (N.O./N.C.)
E8PC-@@@D/T: PNP
E8PC-@@: NPN
30 VDC or less, Class 2, 100 mA max., residual voltage 1 V or less
Analog current output *8
Pressure analog output / Temperature analog output
Current output 4 to 20 mA (maximum load resistance 350Ω or less)
(Display value ± 2% of F.S.)
External input
One-point teaching, zero point adjustment input (selectable, initial status: invalid)
short-circuit current 1.5 mA or less, input time 20 ms or more