Brochure
E5_C General purpose temperature controllers
12
E5GC
E5DC
Item E5GC
Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Sensor input • Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
• Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Control method ON/OFF control or 2-PID control (with auto-tuning)
Control output Relay output SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value)
Voltage output (for driving SSR) Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000
Auxiliary output Number of outputs 1 or 2 (depends on model)
Output specifications SPST-NO relay outputs, 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Indication method 11-segment digital displays and individual indicators
Character height: PV: 10.5 mm, SV: 5.0 mm
Multi SP Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications.
*1
*1
Only four set points are selectable for event inputs.
Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (includ-
ing SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop,
protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple pro-
gramming, moving average of input value, display brightness setting, simple transfer output, and work bit message.
*2
*2
Simple transfer output and work bit message are only for E5GC.
Size in mm (H×W×D) 24×48×93
Item E5DC
Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 4.9 VA max. at 100 to 240 VAC, and
2.8 VA max. at 24 VDC or
1.5 W max. at 24 VDC
Sensor input • Temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
• Analog inputs
Current input (mA): 4 to 20 or 0 to 20
Voltage input (V): 1 to 5, 0 to 5, or 0 to 10
Input impedance Current input: 150 max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Indication accuracy Thermocouple input: (±0.3% of PV or ±1°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Auto-Tuning Yes, 40%/100% MV output limit selection. When using Heat/Cool: Automatic cool gain adjustment
Self-Tuning Yes
Control outputs Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
Voltage output (for driving SSR) Output voltage: 12 VDC ±20% (PNP), max. load current: 20 mA, with short-circuit protection circuit
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Auxiliary outputs Number of outputs 2 (depends on model)
Output specifications SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
Event inputs Number of inputs 1 (depends on model)
External contact input specifications Contact input: ON: 1 k max., OFF: 100 k min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: approx. 7 mA per contact
Setting method Digital setting using front panel keys
Indication method 11-segment digital displays and individual indicators
Character height: PV 8.5 mm, SV: 8.0 mm
Multi SP Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications.
*1
*1
Only two set points are selectable for event inputs.
Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (includ-
ing SSR failure (HB) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop,
protection functions, extraction of square root, MV change rate limit, simple calculations, temperature status display, simple pro-
gramming, moving average of input value, and display brightness setting
Ambient operating temperature –10 to 55°C (with no condensation or icing), for 3-year warranty: –10 to 50°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature –25 to 65°C (with no condensation or icing)
Degree of protection Main unit: IP20, Terminal unit: IP00
Sampling period 50 ms
Size in mm (H×W×D) 96×22.5×85
E5_C_rev05_EN.fm Seite 12 Donnerstag, 30. Oktober 2014 10:40 10
E5_C General purpose temperature controllers
13
USB communication cable E58-CIFQ2
Item E5AC E5CC E5DC E5EC E5GC
E58-CIFQ2
E58-CIFQ2-E –
E58-CIFQ2
E58-CIFQ2-E
Exchange this head for
E5AC/E5DC/E5EC/E5GC adaptation.
E5_C_rev05_EN.fm Seite 13 Donnerstag, 30. Oktober 2014 10:40 10