Datasheet

E5CC-T
75
Characteristics
*1. The indication accuracy of K thermocouples in the 200 to 1300C range, T and N thermocouples at a temperature of 100C max., and U
and L thermocouples at any temperatu res is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermoco
uples at a temperature of 400 to 800C is 3C max. The indication accuracy of the R
and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or
3C, whichever is greater) 1 digit max. The indication accuracy of PL II thermocouples
is (0.3% of PV or 2C, whichever is greater) 1
digit max.
*2. Ambient temperature: 10°C to 23C to 55C, Voltage range: 15% to 10% of rated voltage
*3. K thermocouple at 100C max.: 10C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. External communications (RS-485) and USB-serial convers
ion cable communications can be used at the same time.
*6. Refer to your OMRON website for the most recent information on applicable models.
*7. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Indication accuracy
(at the ambient temperature of 23°C)
Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1
Platinum resistance thermometer: (
0.2% of indication value or
0.8°C, whichever is greater)
1 digit max.
Analog input:
0.2% FS
1 digit max.
CT input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Influence of temperature *2
Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10°C, whichever is greater) 1 digit
max.
Other thermocouple input: (1% of indication value or 4°C, whichever is greater) 1 digit max. *3
Platinum resistance thermometer: (1% of indication value or 2°C, whichever is greater) 1 digit max.
Analog input: 1%FS 1 digit max.
CT input: 5% F
S 1 digit max.
Influence of voltage *2
Influence of EMS.
(at EN 61326-1)
Input sampling period 50 ms
Hysteresis
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Proportional band (P) for cooling
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resistance
Thermocouple: 0.1°C/ max. (100 max.)
Platinum resistance thermometer: 0.1°C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Vibration
Malfunction 10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
Resistance 10 to 55 Hz, 20 m/s
2
for 2 hrs each in X, Y, and Z directions
Shock
Malfunction 100 m/s
2
, 3 times each in X, Y, and Z directions
Resistance 300 m/s
2
, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g, Adapter: Approx. 10 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.61 or higher
Setup Tool port
E5CC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on
the computer. *5
Standards
Approved standards
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
models only.) *6
Conformed standards EN 61010-1 (IEC 61010-1)
EMC
EMI: EN 61326-1 *7
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326-1 *7
ESD Immunity: EN 61000-4-2
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11