Datasheet
E5EC-T/E5AC-T
89
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note:
In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Set 
value
Alarm type
Alarm output operation
Description of function
When alarm value X 
is positive
When alarm value X 
is negative
0Alarm function OFF Output OFF No alarm
1 Upper- and lower-limit *1
*
2
Set the upward deviation in the set point for the alarm upper 
limit (H) and the lower deviation in the set point for the alarm 
lower limit (L). The alarm is ON when the PV is  outside this 
deviation range.
2 
(default)
Upper-limit
Set the upward deviation in the set point by setting the alarm 
value (X). The alarm is ON when the PV is higher than the 
SP by the deviation or more.
3 Lower-limit
Set the downward deviation in the set point by setting the 
alarm value (X). The alarm is ON when the PV is lower than 
the SP by the deviation or more.
4
Upper- and lower-limit 
range *1
*
3
Set the upward deviation in the set point for the alarm upper 
limit (H) and the lower deviation in the set point for the alarm 
lower limit (L). The alarm is ON when the PV is  inside this 
deviation range.
5
Upper- and lower-limit with 
standby sequence 
*
1
*4
A standby sequence is added to the upper- and lower-limit 
alarm (1). *6
6
Upper-limit with standby 
sequence
A standby sequence is added to the upper-limit alarm (2). *6
7
Lower-limit with standby 
sequence
A standby sequence is added to the lower-limit alarm (3). *6
8
Absolute-val
ue upper-
limit
The alarm will turn ON if the process value is larger than the 
alarm value (X) regardless of the set point.
9Absolute-value lower-limit
The alarm will turn ON if the process value is smaller tha n the 
alarm value (X) regardless of the set point.
10
Absolute-value upper-
limit with standby 
sequence
A standby sequence is added to the absolute-value upper-
limit alarm (8). *6
11
Absolute-value lower-limit 
with standby sequence
A standby sequence is added to the absolute-value lower-
limit alarm (9). *6
12
LBA (alarm 1 type only)
- *7
13 PV change rate alarm - *8
14
SP absolute-value 
upper-limit alarm
This alarm type turns ON the alarm when the set point (SP) 
is higher than the alarm value (X).
15
SP absolute-value 
lower-limit alarm
This alarm type turns ON the alarm when the set point (SP) 
is lower th
an the alarm value (X).
16
MV absolute-value 
upper-limit alarm *9
Standard Control Standard Control
This alarm type turns ON the alarm when the manipulated 
variable (MV) is higher than the alarm value (X).
Heating/Cooling 
Control (Heating MV)
Heating/Cooling 
Control (Heating MV)
Always ON
17
MV absolute-v
alue 
lower-limit alarm *9
Standard Control Standard Control
This alarm type turns ON the alarm when the manipulated 
variable (MV) is lower than the alarm value (X).
Heating/Cooling 
Control (Cooling MV)
Heating/Cooling 
Control (Cooling MV)
Always ON
ON
OFF PV
SP
LH
SP
X
ON
OFF PV
SP
X
ON
OFF PV
SP
X
ON
OFF PV
SP
X
ON
OFF PV
SP
LH
ON
OFF PV
SP
LH
ON
OFF PV
*
5
SP
X
ON
OFF PV
SP
X
ON
OFF PV
SP
X
ON
OFF PV
SP
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF PV
0
X
ON
OFF SP
0
X
ON
OFF SP
0
X
ON
OFF SP
0
X
ON
OFF SP
0
X
ON
OFF MV
0
X
ON
OFF MV
0
X
ON
OFF MV
0
X
ON
OFF MV
0
X
ON
OFF MV
0
X
ON
OFF MV